RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES

7

66-1090—2

Final Wiring Check

1. Check the power supply circuit. The voltage and

frequency tolerance must match those of the
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D. A
separate power supply circuit can be required for the
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D. Add
the required disconnect means and overload protection.

2. Check all wiring circuits and complete Static Checkout

in Table 6 before installing the RM7895A,B,C,D/
EC7895A,C; RM7896A,B,C,D on the subbase.

3. Install all electrical connectors.
4. Restore power to the panel.

Table 3. Terminal Ratings.

Terminal

Ratings

No

Description

RM7895/RM7896

EC7895

G

Flame Sensor Ground

Earth G

Earth Ground

a

L2(N)

Line Voltage Common

3

Alarm

120 Vac, 1A pilot duty.

220-240 Vac, 1A pilot duty.

4

Burner Motor

120 Vac, 9.8 AFL, 58.8 ALR
(inrush).

220-240 Vac, 4A at PF = 0.5, 20A inrush.

5

Line Voltage Supply (L1)

120 Vac (+10/-15%),
50 or 60 Hz (+/- 10%).

b

220-240 Vac (+10/-15%)
50 or 60 Hz (

±

10%.)

6

Burner Controller and Limits

120 Vac, 1 mA.

220-240 Vac, 1 mA.

7

Lockout Interlock

120 Vac, 8A run, 43A inrush.

8A at PF = 0.5, 40A inrush, 2A at PF = 0.2.

8

Pilot Valve/Ignition

120 Vac

c

220-240 Vac, 4A at PF = 0.5, 20A inrush.

9

Main Fuel Valve

120 Vac

c

220-240 Vac, 4A at PF = 0.5, 20A inrush.

10

Ignition

120 Vac

c

220-240 Vac, 2A at PF = 0.2.

F(11)

Flame Sensor

60 to 220 Vac, current limited.

60 to 220 Vac, current limited.

12 to 20

Unused

21

2nd Stage Main Valve
(EC7895C, RM7895C,D;
RM7896C,D)

120 Vac

c

220-240 Vac, 4A at PF = 0.5, 20A inrush.

22

Shutter

120 Vac, 0.5A

220-240 Vac

d

a

See Table 2.

b

2000 VA maximum load connected to RM7895A,B,C,D/EC7895A,C/RM7896A,B,C,D Assembly.

c

See Tables 4 and 5.

d

Requires 220-240 Vac, 10 VA minimum, stepdown transformer to operate the shutter.

Table 4. Combinations for Terminals 8, 9, 10 and 21.

Combination No.

Pilot Fuel 8

Main 9

Ignition 10

Delayed Main Valve 21

1

C

F

No Load

No Load

2

B

F

No Load

No Load

3

F

a

No Load

A

No Load

4

F

F

A

No Load

5

F

a

No Load

A

F

6

D

F

A

No Load

7

D

a

No Load

A

D

8

D

D

A

No Load

9

D

a

No Load

A

D

a

RM7895C,D; EC7895C only, jumper terminals 8 to 9.