RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES RELAY MODULES
7
66-1090—2
Final Wiring Check
1. Check the power supply circuit. The voltage and
frequency tolerance must match those of the
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D. A
separate power supply circuit can be required for the
RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D. Add
the required disconnect means and overload protection.
2. Check all wiring circuits and complete Static Checkout
in Table 6 before installing the RM7895A,B,C,D/
EC7895A,C; RM7896A,B,C,D on the subbase.
3. Install all electrical connectors.
4. Restore power to the panel.
Table 3. Terminal Ratings.
Terminal
Ratings
No
Description
RM7895/RM7896
EC7895
G
Flame Sensor Ground
—
—
Earth G
Earth Ground
a
—
—
L2(N)
Line Voltage Common
—
—
3
Alarm
120 Vac, 1A pilot duty.
220-240 Vac, 1A pilot duty.
4
Burner Motor
120 Vac, 9.8 AFL, 58.8 ALR
(inrush).
220-240 Vac, 4A at PF = 0.5, 20A inrush.
5
Line Voltage Supply (L1)
120 Vac (+10/-15%),
50 or 60 Hz (+/- 10%).
b
220-240 Vac (+10/-15%)
50 or 60 Hz (
±
10%.)
6
Burner Controller and Limits
120 Vac, 1 mA.
220-240 Vac, 1 mA.
7
Lockout Interlock
120 Vac, 8A run, 43A inrush.
8A at PF = 0.5, 40A inrush, 2A at PF = 0.2.
8
Pilot Valve/Ignition
120 Vac
c
220-240 Vac, 4A at PF = 0.5, 20A inrush.
9
Main Fuel Valve
120 Vac
c
220-240 Vac, 4A at PF = 0.5, 20A inrush.
10
Ignition
120 Vac
c
220-240 Vac, 2A at PF = 0.2.
F(11)
Flame Sensor
60 to 220 Vac, current limited.
60 to 220 Vac, current limited.
12 to 20
Unused
—
—
21
2nd Stage Main Valve
(EC7895C, RM7895C,D;
RM7896C,D)
120 Vac
c
220-240 Vac, 4A at PF = 0.5, 20A inrush.
22
Shutter
120 Vac, 0.5A
220-240 Vac
d
a
See Table 2.
b
2000 VA maximum load connected to RM7895A,B,C,D/EC7895A,C/RM7896A,B,C,D Assembly.
c
See Tables 4 and 5.
d
Requires 220-240 Vac, 10 VA minimum, stepdown transformer to operate the shutter.
Table 4. Combinations for Terminals 8, 9, 10 and 21.
Combination No.
Pilot Fuel 8
Main 9
Ignition 10
Delayed Main Valve 21
1
C
F
No Load
No Load
2
B
F
No Load
No Load
3
F
a
No Load
A
No Load
4
F
F
A
No Load
5
F
a
No Load
A
F
6
D
F
A
No Load
7
D
a
No Load
A
D
8
D
D
A
No Load
9
D
a
No Load
A
D
a
RM7895C,D; EC7895C only, jumper terminals 8 to 9.