F 10 pneumatic positioner – Greenheck El-O-Matic E and P Series User Manual
Page 2

F 10 Pneumatic Positioner
Where to Find Information
Page
Product Description
1
Operating Principle
2
Installation, Rotary Actuators
- Mechanical
3
- Pneumatic, Double Acting
3
- Pneumatic, Single Acting
4
- Air Supply Requirement
4
Installation, Linear Actuators
- Mechanical installation
5
- Pneumatic installation
6
Calibration
- Initial Settings
7
- Cam Changes
7
- Zero Adjustment
8
- Range Adjustment
8
Trouble Shooting
9
General Specification:
Metric
Imperial
Hysteresis
: 0.6%
Linearity
: 1.0%
Air Flow
: 210 Nl/min (at 6 bar)
: (7.4 SCFM
at 87 psi)
Air Consumption
: 15 Nl/min (at 6 bar)
: (0.6 SCFM
at 87 psi)
Min. volume
actuator
: 0.1 Nl
: 6.1 in
3
Temperature
: -20° to +80° C
: (-4° to +176°F)
Enclosure
: IP54 (option IP65)
: NEMA 3 (option NEMA 4)
Mounting
: VDI/VDE 3845 or
IEC 534/6
Air Entry
: G 1/4"
: (1/4" NPT)
Air Supply
: 1.4 to 8.6 bar
: (21 to 125 psi).
Input Signal
-
Standard
: 0.2 to 1.0 bar
: (3 to 15 psi).
-
Adjustable
: 0.2 to 0.6 bar
: (3 to 9 psi).
: 0.6 to 1.0 bar
: (9 to 15 psi).
Media
: Non-lubricated instrument air, filtered at 25 micron.
: Dew point should be 10°C (18°F) below enviromental temperatur.
: Air quality class 3-2-3 accord. to ISO 8573-1.