1. Smoke Damper requirementS anD

application

Smoke dampers are required to close and prevent

the passage of air and smoke through ducts or
ventilation openings in smoke barriers. Smoke
dampers are also applied in engineered smoke
control systems to establish air pressure differentials
and thereby prevent the spread of smoke. These
dampers are designed to operate with blades running
horizontally. Dampers can be vertically or horizontally
installed at, in accordance with NFPA-90A, or
adjacent to the point where the duct passes thru the
smoke barrier.

2. location of Damper in Ductwork
Place the damper assembly in its proper position

relative to the barrier. The plane of the closed
damper blades must be within 24 in. (610mm) of the
rated smoke barrier and before any duct inlets or
outlets.

3. attaching Damper to the Duct
The damper is flange mounted to the duct, sleeve,

or wall opening with

using #10 sheet metal screws,

1/4 in. (6mm) diameter bolts and nuts, tack or spot
welds, or 3/16 in. (5mm) diameter steel pop rivets.

Attachments must be made at each flange spaced
a maximum of 6 in. (152mm) on centers and a
maximum of 2 in. (51mm) from corners.

4. Sealing the inStallation
The following duct sealants may be used to seal

between the dampers flange and the mating surface:
PA2084T duct sealant adhesive manufactured
by Precision, DP1010 water base duct sealant
manufactured by Design Polymetrics, Grey Pookie
or Ductmate PROseal® in accordance with SMACNA
recommendations.

5. actuator connectionS
Electrical and/or pneumatic connections to damper

actuators should be made in accordance with wiring
and piping diagrams developed in compliance with
applicable codes, ordinances and regulations.

Document number 472664

inStallation inStruction Supplement

Refer to:
‘Installation Instructions for SMD, SESMD, SSSMD, SMDR,
SESMDR, and SSSMDR series Models’ (Part #)
for additional details.

flange mounted installation

SmD-xxx, SeSmD-xxx,

SSSmD-xxx Series

Smoke Dampers

“ul claSSifieD

(see complete marking on product)”

“ul claSSifieD to canadian safety standards

(see complete marking on product)”

Standards UL 555 & 555S

Classifications Filed at UL under Listing #R13317

Damper model

Maximum Single

Section Size

in. (mm)

Maximum Overall

Size for Multiple

Section Dampers

in. (mm)

SMD-301, 302

32 x 50

(813 x 1270)

128 x 100 or 256 x 50

(3251 x 2540) or

(6502 x 1270)

SMD-301M, 302M

32 x 50

(813 x 1270)

128 x 100 or 256 x 50

(3251 x 2540) or

(6502 x 1270)

SMD-401

48 x 60

(1219 x 7315)

192 x 72, 48 x 288,

or 384 x 36

(4877 x 1829,

1219 x 7315 or

9754 x 914)

SMD-401M

48 x 36

(1219 x 914)

144 x 36

(3658 x 914)

®