counterbalance adjustment instructions cont...

5. Open damper and recheck full open operation.

Readjust per step 3 if necessary. Recheck full closed
position (step 4) as any modification at one position
has a slight impact on the other.

6. Tighten all counterweight and arm fasteners securely.

component

applicable

Model

galvanized

Part number

Stainless

Part number

Axle Adapter, 3/8” to 3/4”
square OD

HB-110, HB-120

370120

416343

3/4” Crankarm

All

652982

687738

3/8”-16x2 Crankarm Bolt

All

415882

415924

3/8”-16 Hex Nut for
Crankarm

All

415457

415799

Short Counterweight Arm
(81/2 in. )

All

657344

689404

Long Counterweight Arm
(121/2 in. )

All

657343

683951

3/8”-16 set screw for
short/long arm

All

415050

415763

3/8” -16 Weldnut/Hex nut
for short/long arm

All

415127

415799

Counterweight plate,
21/2” x 31/2”

All

653143

687636

Counterweight plate,
31/2” x 31/2”

All

653142

687635

1/4”-20 Serrated Flange Nut

All

415455

415575

1/4”-20 x 3/4” Bolt

All

415490

415573

1/4”-20 x 11/4” bolt/
11/2” bolt

All

415973

416103

Standard components

7. Test damper closure by opening damper blades and

releasing from 1/4, 1/2, 3/4 and full open position.
Damper should close from all positions without
assistance.

469620• HB Series Rev. 2, October 2012

Copyright 2012 © Greenheck Fan Corporation

As a result of our commitment to continuous improvement, Greenheck reserves the right to change

specifications without notice.

Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in

the Library under Warranties.

®

Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: [email protected] • Website: www.greenheck.com

Our Commitment