background image

4

Supply Wire Size

(Not More Than 6 Conductors in Single Conduit

1

)

AWG or MCM

Max. Heater Line Current

2

Copper

3

Copper

3

AWG or MCM

Max. Heater Line Current

2

14

12

0000

184

12

16

250

204

10

24

300

228

8

36

350

248

6

52

400

268

4

68

500

304

3

80

600

336

2

92

700

368

1

104

750

380

0

120

800

392

00

140

900

416

000

160

1000

436

1

For 7-24 conductors in raceway or cable reduce allowable heater line currents to 87 1/2 % of those shown
above.

2

Based on 30

o

C (86

o

F) ambient temperature, for higher ambient temperature see N.E.C. table 310-16 and 310-

18 Note 13.

3

Based on 80% of ratings in table 310-16 N.E.C. for 75

o

C insulation.

De-rated Wattage For Low Voltage

Heater

Line

% of Heater

Heater

Line

% of Heater

Voltage

Voltage

Wattage and BTU

Voltage

Voltage

Wattage and BTU

480

460

92

208

200

92

440

84

190

83

277

265

92

120

115

92

254

84

110

84

240

230

92

220

84

208

75

200

69

Effect of Low Voltage on Wattage and B.T.U.:

The heating elements may be used on voltages lower than the design voltage of the heater; however, the wattage
and B.T.U. output will be reduced to the percentages listed in the table below.