Greenheck Microprocessor Controller Start-Up Guide v3.0 (469710) User Manual

Microprocessor controller start-up guide

Advertising
background image

®

UNIT START COMMAND: For manual operation
jumper R to G on unit (BMS or Time Clock – refer to
Controller IOM) The controller will display a Start-Up
screen that shows the program version along with
the specifi c code for the unit. This code should be
verifi ed with the “DDC Setup Code”

on the unit’s

wiring diagram.

Outdoor air and Exhaust air (optional) damper

actuators are powered

Energy wheel is powered

Exhaust fan starts after a 15 second delay

Supply fan starts fi ve seconds after the

exhaust

fan.

UNIT STOP COMMAND:

For manual operation open R to G on unit (BMS or Time Clock – refer to Controller IOM)

Supply fan, exhaust fan are de-energized.

Wheel, outdoor air and exhaust air damper (optional) are de-energized and dampers spring return closed.

UNIT STATUS:

From the start-up screen, press the blinking ESC button

After approximately three minutes of inactivity the controller will display a “Unit Status” screen describing the real-time mode the
unit is operating in. Below is a description of operational sequences the unit could be executing

Initial Delay

Outside: 000.0 F

Supply: 000.0 F

Cold Coil: 000.0 F

G

GO

Wire Power to G and GO

Shows

Unit

Status

Displays

Temperatures

Part #469710

Microprocessor Controller

Start-Up Guide

Unit Status

Possible Operation Sequence

INITIAL DELAY:

15 second delay before dampers open

OPENING DAMPERS:

Dampers will open for programmed time (Default: 10 sec.), wheel energized

EXHAUST FAN STARTING:

Power to Exhaust Fan

SUPPLY FAN STARTING:

Power to Supply Fan SYSTEM ON: Startup Sequence is complete

DEFROST MODE ACTIVE:

Timed exhaust, preheat, or modulating wheel

SYS ON-ECONOMIZER:

Wheel ON/OFF or modulating to maintain discharge temperature

SYS ON-HEATING:

Unit heating to meet desired supply temperature

SYS ON-COOLING:

Unit cooling to meet desired supply temperature

SYS ON-DEHUMIDIFYING:

Unit cooling to meet desired post cooling-coil temperature

SYS ON-DEHUM & REHEAT:

Unit cooling to dehumidify-reheating to desired supply temperature

UNOCCUPIED-UNIT OFF:

Unit off during unoccupied mode

UNOCCUPIED-HEATING:

Unit heating recirculated air to maintain unoccupied room heating temperature

UNOCCUPIED-COOLING:

Unit cooling recirculated air to maintain unoccupied room cooling temperature

MANUAL OVERRIDE!!:

The system is in Manual Override operation

REMOTE OFF:

The unit has been turned off from a remote display panel

PRESS ALARM BUTTON!:

An alarm is occurring

CONTROLLER BUTTONS

In the event that the unit is not functioning normally, the alarm light will turn red. Press the button once to see which alarm
occurred. Press again for alarm options. Please refer to Controller IOM for more information on specifi c alarms.

The program button is used to setup the control loops, staging, passwords, etc. A qualifi ed technician should perform
adjustments to these parameters. (A level 2 password must be entered to alter any of the factory programming).

Escape button returns you to the main menu where the following menus can be accessed: Unit Status, Set Points, Manual
Overrides, I/O Setup, Clock Setup, Misc Info, and Unit On/Off.

Use the up and down arrow buttons to scroll through display screens, and to set the values of the control parameters.

Use the return button to confi rm the set data.

For additional information see the Installation and Operation Manual (IOM) shipped with this unit. If missing, contact the factory or
visit greenheck.com

#469710 Microprocessor Start-Up Guide

Rev. 1, February 2007

Copyright © 2007

Advertising