Greenheck TCB/TCBRU/TCBRS (456557) User Manual

Greenheck, Installation operation and maintenance manual, Read and save these instructions

Advertising
background image

TCB

Tubular Centrifugal Inline Fan

TCBRU

Centrifugal Upblast Fan

TCBRS

Centrifugal Roof Supply Fan

RECEIVING

Greenheck models TCB, TCBRU, and TCBRS are thoroughly inspected and test run at the factory. Items such as proper wheel
alignment, balance, vibration and workmanship are analyzed by quality control personnel using state-of-the art equipment.
However, damage may occur during handling and shipping. Therefore, it is important that the unit be carefully inspected for
visible and concealed damage before beginning installation. In addition, check to see that all accessory items are accounted for.

STORAGE - Indoor and Outdoor

When a fan is to be stored for a period of time, it must be protected from dirt and moisture. Use of a tarp to cover the unit will
aid in keeping it clean and dry, but avoid using a black plastic tarp as it will promote condensation. Improper storage which
results in damage to the fan will void the warranty. If the storage period is lengthy, the wheel and motor should be rotated
periodically and the bearings purged with fresh grease. In humid, dusty, or corrosive atmospheres, rotate the fan and purge the
bearings once a month. Under normal conditions, this procedure should be repeated once every three months.

TCBRU Roof Upblast

Level 1 & 2

TCB Inline

Level 1 & 2

TCBRS Roof Supply

Level 1 & 2

HANDLING

Fans are to be rigged by either the lifting
brackets provided or by the skid when a
forklift is used. All TCB Inline models have
mounting brackets located at the ends of
the fan housing with which slings can be
attached (Fig. 1). All TCBRU Roof Upblast
models can be lifted by lifting lugs located
above the motor cover of the fan (Fig. 2). All
TCBRS Roof Supply fans can be lifted by
lugs located on the hood rails (Fig. 3).

Fans should NOT be lifted by the shaft,
housing, motor, belt guard, or any
accessories.

Fig. 1

Fig. 3

Fig.2

GREENHECK

P.O. BOX 410 SCHOFIELD, WISCONSIN 54476-0410

PH. 715-359-6171

®

READ AND SAVE THESE INSTRUCTIONS

PN 456557

Installation Operation and Maintenance Manual

REPORT ANY DAMAGED EQUIPMENT TO THE SHIPPER IMMEDIATELY!