DOCUMENT NUMBER 479869

MOUNTING KIT FOR ACTUATORS

Belimo and Honeywell models

Installation, Operation, and Maintenance Instructions

These instructions apply to the internal or external field replacement of mounting hardware for direct drive
actuators (Belimo and Honeywell [except MS7505 and MS8105 series] ) on Greenheck control dampers when
they are duct mounted or sleeved.

PART NO. 872700: INTERNAL MOUNT - 1/2 IN. PIN OR JACKSHAFT

3-V Blade

Steel Airfoil Blade

Aluminum Airfoil Blade

Instructions

1. Have damper in desired fail position.
2. Drill (2) 0.203 inch holes in the first blade (when one

or two blade damper) or third blade (more than a two
blade damper) at a location as shown above for the
blade type you have.

3. Attach blade drive lever (item #13) using two fasteners

(see list above based on blade type). Note: Shaft (item
#4) needs to be centered with the centerline of the
blade.

4. Fasten actuator bracket (item #1) to the left jamb of

damper frame using (1) thread cutting screw in top tab
of bracket (0.203 in. hole is required). Note bottom tab
does not get a fastener. Install (2) 1/4 -20 x 1/2 studs
(item #15) and nuts (item #14) through holes in damper

frame. Snap bearing (item #12) into internal actuator
bracket.

5. Slide 1/2 in. diameter shaft (item #4) slightly through

the anti-rotation bracket (item #5). Install crankarm
(item #3) and drive link (item #2) onto the 1/2 in.
diameter shaft (item #4) and install e-clip (item #6) to
lock drive link (item #2) on the crankarm (item #3).After
the crankarm is installed, slide 1/2 in. shaft through the
bearing (Item #12).

6. Install shoulder bolt (items #8 or 10) to the anti-rotation

bracket (item #5) using nut (item #9 or 11). Bolt
location will vary depending on the actuator model.

7. Slide the anti-rotation bracket (item #5) over the 1/2

in. shaft. Fasten to actuator bracket (item #1) using
thread cutting screws (item #7). Attach actuator to

Tools Required:

Wrenches: (1)

7

16

in., (1)

3

8

in., (1)

9

16

in.

(1) Ratchet with

3

8,

7

16, 9

16

in. deepwell socket

(1)

1

8

in. Allen wrench,

(1) Drill with

3

8

in. and 9/32 in. nut driver,

(1) .203 dia. drill bit

!

!

WARNING

Equipment Damage or Electrical Power Hazard.
Line voltage can cause death or serious injury
and short circuit equipment. Disconnect power
supply before installation.

®