Network Interface Controller for Tempered Air Products

Points List • Modbus / BACnet®

Type

Modbus-RTU/TCP/IP

Network Address: 1

BACnet IP/Ethernet BACnet MSTP
Device Instance: 77000(default)

Read

Write

Description

Address

Address

Name

Units

Analog

40002

1

Outside_Air_Temp

°F

R

Outdoor Air Temp (###.#°F)

Analog

40003

2

Supply_Air_Temp

°F

R

Supply Air Temp (###.#°F)

Analog

40004

3

Cold_Coil_Leaving_Temp

°F

R

Cold Coil Temp (###.#°F)

Analog

40005

4

Return_Air_Temp

°F

R

Return AirTemp (###.#°F)

Analog

40006

5

Exhaust_Discharge_Temp

°F

R

Exhaust Discharge Temp (###.#°F)

Analog

40007

6

OA_After_Wheel_Temp

°F

R

Outdoor Air After Wheel Temp (###.#°F)

Analog

40008

7

Room_Temp

°F

R

Room Temp (###.#°F)

Analog

40011

10

Heat_Output

percent

R/W

Heater output (0-100%)

Analog

40012

11

Cool_Output

percent

R/W

Cooling output (0-100%)

Analog

40013

12

VFD_Supply_Output

percent

R/W

VFD Supply Fan Output (0-100%)

Analog

40014

13

VFD_Exhaust_Output

percent

R/W

VFD Exhaust Fan Output (0-100%)

Analog

40015

14

VFD_Wheel_Output

percent

R/W

VFD Wheel Output (0-100%)

Analog

40016

15

RA_Damper_Output

percent

R/W

Return Air Damper Output (0-100%)

Analog

40017

16

Outdoor RH

percent relative

humidity

R

Outdoor RH

Analog

40018

17

Supply_VFD_Mointor

volts

R

Supply VFD Monitor Signal (Vdc)

Analog

40019

18

Exhaust_VFD_Monitor

volts

R

Exhaust VFD Monitor Signal (Vdc)

Analog

40027

26

User_Define_B1_Analog_Input

no-units

R

User Define B1 Analog Input

Analog

40028

27

User_Define_B2_Analog_Input

no-units

R

User Define B2 Analog Input

Analog

40029

28

User_Define_B5_Analog_Input

no-units

R

User Define B5 Analog Input

Analog

40030

29

User_Define_B6_Analog_Input

no-units

R

User Define B6 Analog Input

Analog

40031

30

User_Define_Y4_Analog_Output

no-units

R/W

User Define Y4 Analog Output

Integer

40216

1007

CO2_Level

ppm

R

CO2 Levels (ppm)

pCOe Analog Variables

Analog

40022

21

pCOe_Analog_Input_Probe_Value_1

°F or Percent

R

pCOe Analog Input Probe Value 1

Analog

40023

22

pCOe_Analog_Input_Probe_Value_2

°F or Percent

R

pCOe Analog Input Probe Value 2

Analog

40024

23

pCOe_Analog_Input_Probe_Value_3

°F or Percent

R

pCOe Analog Input Probe Value 3

Analog

40025

24

pCOe_Analog_Input_Probe_Value_4

°F or Percent

R

pCOe Analog Input Probe Value 4

Analog

40026

25

pCOe_Analog_Out

percent

R/W

pCOe Auxillary Analog Out (0-10V)

Type

Address

Address

Name

Inactive_Text

Active_Text

Read Write

Description

Digital

10011

10

Unit_Start_Stop

Stop

Start

R/W

Unit start/stop command

Digital

10012

11

Reset_Alarms

Don't Reset

Reset Alarms

R/W

Reset alarms command

Digital

10015

14

Cooling_Stg1_Command

Off

On

R/W

Cooling Stage 1 Command

Digital

10016

15

Cooling_Stg2_Command

Off

On

R/W

Cooling Stage 2 Command

Digital

10017

16

Heat_Stg1_Command

Off

On

R/W

Heating Stage 1 Command

Digital

10018

17

Occ_Unocc_Command

Off

On

R/W

Occupied/unoccupied Command

Digital

10019

18

Remote_Exh_Fan_Command

Off

On

R/W

Remote Exhaust Fan Command

Digital

10020

19

HGRH_Command

Off

On

R/W

Hot Gas Reheat Command

Digital

10021

20

Global_Alarm

Off

Alarm

R

Global alarm indication (active when there is at least one alarm)

Digital

10022

21

Frost_Status

Off

On

R

Frost Status

Digital

10023

22

Econ_Status

Off

On

R

Econ Status

Digital

10024

23

Fan_Proving_Status

Off

On

R

Fan Proving status

Digital

10026

25

Dirty_filter_Status

Clean

Dirty

R

Dirty filter status

Digital

10027

26

Wheel_Status

Ok

Not Ok

R

Wheel status-Not Ok=Wheel not running when commanded on

Digital

10028

27

Supply_air_low_limit

Off

Alarm

R

Supply air temperature low limit alarm

Digital

10029

28

Sensor_B1_out_of_range

Off

Alarm

R

Sensor B1 out of range

Digital

10030

29

Sensor_B2_out_of_range

Off

Alarm

R

Sensor B2 out of range

Digital

10031

30

Sensor_B3_out_of_range

Off

Alarm

R

Sensor B3 out of range

Digital

10032

31

Sensor_B4_out_of_range

Off

Alarm

R

Sensor B4 out of range

Digital

10033

32

Sensor_B5_out_of_range

Off

Alarm

R

Sensor B5 out of range

Digital

10034

33

Sensor_B6_out_of_range

Off

Alarm

R

Sensor B6 out of range

Digital

10035

34

B5 _User_Alarm

No Alarm

Alarm

R

B5 User Input Alarm

Digital

10036

35

B6_User_Alarm

No Alarm

Alarm

R

B6 User Input Alarm

Digital

10039

38

User_Define_B5_DI

Open

Closed

R

User Define B5 Digital Input

Digital

10040

39

User_Define_B6_DI

Open

Closed

R

User Define B6 Digital Input

Digital

10041

40

User_Define_NO1_DO

Off

On

R/W

User Define NO1 Digital Output

Digital

10042

41

User_Define_NO2_DO

Off

On

R/W

User Define NO2 Digital Output

Digital

10043

42

User_Define_ID2_DI

Open

Closed

R

User Define ID2 Digital Input

pCOe Analog Variables

Digital

10052

51

pCOe_Auxiliary_Digital_Input_1

Off

On

R

pCOe Auxillary Digital Input1

Digital

10053

52

pCOe_Auxiliary_Digital_Input_2

Off

On

R

pCOe Auxillary Digital Input2

Digital

10054

53

pCOe_Auxiliary_Digital_Input_3

Off

On

R

pCOe Auxillary Digital Input3

Digital

10055

54

pCOe_Auxiliary_Digital_Input_4

Off

On

R

pCOe Auxillary Digital Input4

Digital

10056

55

pCOe Auxillary Digital Output1

Off

On

R/W

pCOe Auxillary Digital Output1

Digital

10057

56

pCOe Auxillary Digital Output2

Off

On

R/W

pCOe Auxillary Digital Output2

Digital

10058

57

pCOe Auxillary Digital Output3

Off

On

R/W

pCOe Auxillary Digital Output3

Digital

10059

58

pCOe Auxillary Digital Output4

Off

On

R/W

pCOe Auxillary Digital Output4

®

Advertising