Greenheck Programming Sure-Aire K-Factor (478758) User Manual

Density corrections, Programming sure-aire, Calculating flow from differential pressure

Advertising
background image

Density Corrections

Air density,

, is affected by elevation and temperature. The Greenheck Sure-Aire Differential Pressure Controllers

allow the user to input the elevation for the application. This elevation input automatically updates the density
used for the flow calculation.
The Remote Temperature Sensor will adjust the air density value in the controller based on the sensor
measurement when Temperature Compensation is set to ‘Yes’. This density compensation will affect the flow rate
displayed on the controller. If Temperature Compensation is set to ‘No’, the air density value will be a function of
standard air (70°F/21°C).
The density being used by the Sure-Aire controller can be viewed on the main menu by scrolling up or down
through the settings.

Greenheck Part Number

Controller ∆P Range

(inches W.C.)

Pmax

(inches W.C.)

100-240 VAC 24 VAC / VDC

384799

384986

0-8.30

8.30

384800

384987

0-22.14

22.14

384801

384988

0-41.52

41.52

384802

384989

0-83.04

83.04

384803

384990

0-138.40

138.40

Programming Sure-Aire™

Greenheck’s Sure-Aire™ Differential
Pressure Controller provides either a
2-10 Vdc or 4-20 mA electrical output
signal. The output signal is linearly
proportional to the pressure range of
differential pressure controller. The
ranges for Greenheck’s Sure-Aire
controllers are listed in the table.

Calculating Flow from Differential Pressure

The volumetric flow through the fan (cfm) can be calculated from the equation:

where K is the K-factor for the specific fan model and size, ∆P is the measured differential pressure across the
inlet cone (inches W.C.), and  is the air density (lb/ft

3

). K-factors for Greenheck models are found on the back of

this document.

CFM = K

∆P

Calculating Flow from Voltage Signal

If using a 2-10 Vdc output signal from a differential pressure controller, this equation can be used to calculate the
flow:

where V is the output voltage of a 2-10 Vdc transmitter and P

max

is the maximum pressure range of the controller

being used (inches W.C.).

CFM = K

(V - 2) P

max

8

Calculating Flow from Current Signal

If using a 4-20 mA output signal from a differential pressure controller, this equation can be used to calculate the
flow:

where mA is the output current of a 4-20 mA transmitter and P

max

is the maximum pressure range of the

controller being used (inches W.C.).

CFM = K

(mA - 4) P

max

16

1

Programming Sure-Aire™

®

®

Document 478758

Programming Sure-Aire™

Advertising