4:1 Modulating Furnace Will Not Light

In all cases, verify correct terminals as shown on the unit-specific wiring diagram.

Troubleshooting

24 VAC across

terminals S and T?

Discharge temperature was above high limit control (HLC1)

Wait for high limit to cool and reset

Inlet air sensor contact open

Adjust inlet air sensor setting (refer to 4:1 Modulation Start-Up section)

Furnace controller (SC1) defective

Replace furnace controller (SC1)

24 VAC across 22 and 21?

Heat transformer (TR2) fault

Replace heating transformer

No

No

Yes

Yes

N.O. contact on

heat relay (RH) closed?

Heat relay (RH) is not energized

Check for loose connections. Repair or replace heat relay (RH)

No

Yes

24 VAC across W1 and L?

Heat switch (S4) open or not wired

Close or replace heat switch (S4)

No

Yes

24 VAC across R and L?

Main disconnect (DS1) open or defective

Close, repair or replace

Main transformer (TR1) fault

Replace main transformer

No

Yes

Continues on next page...

DT1 displayed

on furnace controller (SC1)?

Discharge air sensor (TS2) not wired or defective

Wire or replace discharge air sensor (TS2)

Yes

No

OT1 displayed

on furnace controller (SC1)?

Outdoor air sensor (TS1) not wired or defective

Wire or replace outdoor temperature sensor (TS1)

Yes

No

Blank screen

on furnace controller (SC1)?

Furnace controller (SC1) defective or not powered

Replace or wire furnace controller (SC1)

Yes

No