Greenheck Smoke Detector D4120 (Data Sheet) User Manual

Wire photoelectric duct smoke detector

Advertising
background image

Agency Listings

4-Wire Photoelectric Duct

Smoke Detector

The InnovairFlex

Series are the only duct smoke

detectors flexible enough to fit configurations from

square to rectangular and everything in between.

Features

Photoelectric, integrated low-flow technology

Air velocity rating from 100 ft/min to 4,000 ft/min (0.5 m/s to 20.32

m/sec)

Versatile mounting options: square or rectangular configuration

Plug-in sensor offers superb false alarm immunity and the latest

sensor technology

Broad ranges for operating temperature (–4°F to 158°F) and

humidity (0% to 95% non-condensing)

Patented sampling tube installs from front or back of the detector

with no tools required

Increased wiring space with a newly added ¾-inch conduit

knockout

One easy-access Test/Reset button and improved LED status

Patented interconnect feature for multi-fan shutdown

New high contrast terminal designations

Built-in short circuit protection from operator wiring errors

Field selectable settings for configuring the detector

Two DPDT Form-C relay contacts

24 VAC/DC or 120 VAC

Backward compatibility with existing Innovair products, including

remote accessories

The InnovairFlex D4120 4-wire photoelectric duct smoke
detector features a pivoting housing that fits both square and
rectangular footprints and mounts to round or rectangular ductwork.
This unit senses smoke in the most challenging conditions, operating
in airflow speeds of 100 to 4,000 feet per minute, temperatures
of –4°F to 158°F, and a humidity range of 0 to 95 percent (non-
condensing). A plug-in sensor head offers improved false alarm
immunity and simple installation, testing, and maintenance. An
improved cover design isolates the sensor head from the low-flow
feature for simple maintenance.

The InnovairFlex housing provides ample wiring space, a ¾-inch
conduit knockout, and built-in short circuit protection to prevent
damage to sensitive components during installation. High contrast
terminal designations make wiring easy. With its 2:1 sensor-to-power
capability, the power board of the D4120 may be used to monitor
a second sensor, D4S, simultaneously (i.e., supply and return side).
As many as 50 InnovairFlex detectors can be interconnected. When
one unit senses smoke, all interconnected detectors will switch
their relays; only the detector sensing smoke will go into alarm, thus
pinpointing the fire source.

An easy-access Test/Reset button makes it possible to test the unit
with the cover on. Three DIP switches can be used to configure field
selectable settings: cover tamper delay, number of sensors to be
controlled, and shut down on trouble option. Each power board
has two LEDs that can be used to indicate the status of connected
sensors, and a quick reference imprinted on the cover explains the
LED status indications (Standby, Maintenance, Trouble, and Alarm).
The InnovairFlex duct smoke detector can be customized to meet
local codes and specifications without additional wiring. The new
InnovairFlex product line is compatible with all previous Innovair
models, including remote test accessories.

WARNING: Duct smoke detectors are NOT a substitute for open
area smoke detectors;

NOT a substitute for early warning detection;

NOT a replacement for a building’s regular fire detection system.
Refer to NFPA 72 and 90A for additional information.