Greenheck Vari-Green Control - Indoor Air Quality - Temp/Humidity (475573) User Manual

Control indoor air quality–temp/humidity, Installation, operation and maintenance manual, Temperature and humidity controller

Advertising
background image

PN 475573

Vari-Green

®

Control

Indoor Air Quality–Temp/Humidity

1

Installation, Operation and Maintenance Manual

Please read and save these instructions for future reference. Read carefully before attempting to assemble,

install, operate or maintain the product described. Protect yourself and others by observing all safety

information. Failure to comply with instructions could result in personal injury and/or property damage!

The Temperature and Humidity Controller is

specifically designed to control a Vari-Green fan

motor. The Temperature and Humidity Controller

will sense the temperature and humidity in the

space and will automatically adjust the speed of

a supply or exhaust fan to adjust the ventilation

rate accordingly. The temperature measurement

will be compared to a field adjustable temperature

setpoint, processed through a Proportional/Integral/

Derivative (PID) control algorithm to produce a 2

to 10 VDC fan motor control output. The humidity

measurement will be compared to a field adjustable

humidity setpoint, processed through a PID control

algorithm to produce a 2 to 10 VDC fan motor

control output. If the unit is in temperature only

mode the temperature algorithm’s output shall be

used to provide the fan motor control output. When

the unit is in humidity-only mode the humidity

algorithm’s output shall be used to provide the

fan motor control output. When the unit is in

temperature and humidity mode the algorithm with

the greatest output shall be used to provide the fan

motor control output.

When all active algorithms are satisfied, the output

voltage shall be set to its lowest value, 2 VDC. If

the temperature is 1°F below the temperature

DANGER

Always disconnect, lock and tag power source before

installing or servicing. Failure to disconnect power

source can result in fire, shock or serious injury.

CAUTION

When servicing the fan, motor may be hot enough

to cause pain or injury. Allow motor to cool before

servicing.

CAUTION

Precaution should be taken in explosive

atmospheres.

Only qualified personnel should install this product.

Personnel should have a clear understanding of

these instructions and should be aware of general

safety precautions. Improper installation can result

in electric shock, possible injury due to coming in

contact with moving parts, as well as other potential

hazards. Other considerations may be required

if high winds or seismic activity are present. If

more information is needed, contact a licensed

professional engineer before moving forward.

Temperature and Humidity Controller

General Safety Information

setpoint in

temperature control

and the humidity

is 3% below the

humidity setpoint in

humidity control or

both in temperature

and humidity control,

the voltage output

may be set to zero

(optional cutout

mode). The unit

will resume normal

fan operation if

the temperature

changes by 1°F or

the humidity changes by 5%.

Ventilating based on the temperature and humidity

measurements assures that the space will not be

over or under ventilated while using the Vari-Green

motor technology to operate quietly and efficiently.

The Temperature and Humidity Controller has

adjustments for setpoint, minimum and maximum

fan speed. The fan speed and temperature or

humidity level are available as an analog output to

be read by a building

Advertising