Infloor TC 204 Heating Controller User Manual

Page 11

Advertising
background image

Optimization
Menu 2

W.PR

OPT1

0 - 40

Default 20

Skip this line initially.

The colder it is outside and/or the further the room temperature is below set point the sooner the controller will

start the warm-up cycle. The number in this line is a constant in the equation the TC204 uses to calculate the

warm-up time. If the building warms up too soon, lower it to 15; if the building isnʼt warm soon enough, increase

this number to 25. If you set this line to 0 there is no warm-up cycle at all.
Calibration

Menu 12

CAL.

You can calibrate the temperature sensors used in the TC204.

R1

-9.5 to 9.5 degrees

Room Temperature Sensor Calibration

R2

-9.5 to 9.5 degrees

Second Room Temperature (if used)

OUTD

-9.5 to 9.5 degrees

Outdoor Temperature Sensor Calibration.

SEC/D

-9.9 to 9.9 seconds per day

If the clock runs fast or slow it can be adjusted here. If it is slow add a positive adjustment. If the clock gains one

minute per month, make the adjustment -2.0.
Daylight Savings Time

Menu 12

CAL

SUM

Month 1 - 12 Day 1 - 31

Begin Daylight Savings Time. The first pair of digits is the month and the second is the day of the month.

The clock will move forward one hour at 2:00 am on the date you set.

WIN

Month 1 - 12 Day 1 - 31

End Daylight Savings Time. Set it the same way as SUM above. If you donʼt want daylight savings time set both

SUM & WIN to 0000.
Time

Menu 12

CAL

24h

0 or 1

Default 0 (12 hour time)

Set this to 1 if you want 24 hour (military) time, 0 for 12 hour time. In 12 hour time P.M. shows as 3 dots between

the hours and minutes.
Temperature Scale

SEL.ºF

0 or 1

Default 1 (F)

Set this to 1 if you want readouts in Fahrenheit. Not all temperatures can be set or read in F.

O.RES

0 or 1

The readout of the minimum outdoor temperature can be reset manually or automatically. If you want the readout

to reset automatically every day set this line to 1.
Date Program

Menu 3

D.PRO

You can set up to 4 events that override the weekly program. These can be set up to a year in advance. You

can, for example, set a long term setback for a vacation.
Extra Output

Menu 4

X.OUT

There is an extra output that can be activated by either time or outdoor temperature or both.
Logging Measured Values

Menu 5

LOG

You can keep a log of up to 96 values of the outdoor temperature or the supply water temperature or the room

temperature at intervals up to 1 hour apart.