Infloor TC 204 Heating Controller User Manual

Page 7

Advertising
background image

Go to Menu 8 CURVE
There are 3 adjustable values in this menu.
Curve Design

When you use a room sensor the reset curve is self adjusting. You need this section only if you donʼt use a room

sensor and the default curve does not work for your region.
- 10C1

32º F - 248º F

Default 140º F

Supply water temperature at 14º F (- 10º C) outside temperature
+10C1

32º F - 248º F

Default 86º F

Supply water temperature at 50º F (+10º C) outside temperature
The sample reset schedule shown in the chart is the default. To set +10C1 (50º F) & -10C1 (14º F) select the

water temperature you want at those outside temperature on the vertical F scale.
Suggested Initial Settings

Leave +10C1 at 86º. At 50ºF outside the supply temperature will be 86º F.

Set -10C1 so that at the outside design temperature in your area the supply temperature will be near the maxi-

mum temperature allowed in your system.

7

60º F

50º F

40º F

30º F

20º F

10º F

0º F

Outdoor Temperature

100º

120º

140º

160º

180º

200º

-10º F

-20º F

14

S

u

p

p

ly

W

a

te

r

T

e

m

p

e

ra

tu

re

80º

10º C

-10º C

F

190º

170º

150º

130º

110º

90º

70º

Adjustments
Building is always cold

Raise both settings

Building is always warm

Lower both settings

Building gets colder as it gets colder outside

Raise -10C setting

Building gets warmer as it gets colder outside Lower -10C setting
Automatic Curve Adjustment
AUTO

1 or 0 Default 1

When you use a room sensor this should be set at 1. 0 means the curve doesnʼt adapt.

Set it at 0 if there is no room sensor.

Cout1

Calculated Value

All other Menu 8 items are inactive.