Venting installation instructions, Continued – Desa (V)K36EN SERIES User Manual

Page 10

Advertising
background image

www.desatech.com

111924-01D

10

Figure 15 - Horizontal Termination Configuration for Corner

Installation Using One 90° Elbow

Square

Termination

Wall

Firestop

Not to Exceed

(H) Limits

As Required for (V)

See Chart for Pipe

Section Required

45°

Elbow

90° Elbow

90° Elbow

Square

Termination

Wall

Firestop

45° Elbow

12" Minimum

Not to Exceed

(H) Limits

Square Termination

Vertical (V) Horizontal (H)

32

3

/

4

" min. 17" max.

Horizontal High

Wind Square

Termination

Wall Firestop

45° Elbow

CORNER AND ALTERNATE INSTALLATION
Recommended Applications:
• Corner ground floor installation

• Ground floor installation where pipe vents horizontally through

wall (over 12" horizontal pipe)

• Basement installation where one foot clearance from ground to

termination is possible

VENTING INSTALLATION

INSTRUCTIONS

Continued

Adjustable

Pipe 12" Max.

Figure 14 - Horizontal Termination Configuration for Square

and Round Terminations

45° Elbow

Wall

Firestop

Horizontal

Round

Termination

Exterior Portion of

Wall Firestop (Round

Termination Only)

Horizontal termination Configurations

Figures 14 through 18 show different configurations and alterna-

tives for venting with horizontal termination. Each figure includes

a chart with critical minimum and maximum dimensions which

MUST be met. IMPORTANT: If using a venting configuration of

only horizontal venting with no vertical run, a 1/4" rise for every

12" of run toward the termination is required.

WARNING: Never run vent downward as this may

cause excessive temperatures which could cause a

fire. Operation of improperly installed and maintained

venting system could result in serious injury, property

damage or loss of life.

GROUND FLOOR INSTALLATION
Recommended Applications:
• Installation using cabinet surrounds

• Through the wall using round or square termination (up to 12"

horizontal pipe)

• NOT FOR CORNER INSTALLATION

Required

Vertical (V) Vertical Pipe

Horizontal (H)

*43

1

/

2

" min.

None

30" max.

54

1

/

2

" min.

1 ft.

48" max.

66

1

/

2

" min.

2 ft.

60" max.

78

1

/

2

" min.

3 ft.

84" max.

90

1

/

2

" min.

4 ft.

20' max.

*

Ground Floor Corner Venting