Troubleshooting – Desa (V)K36EN SERIES User Manual

Page 25

Advertising
background image

www.desatech.com

111924-01D

25

TROUbLEShOOTING

Note:

All troubleshooting items are listed in order of operation.

The two most common causes of a malfunctioning gas appliance are:

1. Loose wiring connections

2. Construction debris clogging the pilot and/or gas control valve filter

WARNING: Turn off heater and let cool before ser-

vicing. Only a qualified service person should service

and repair heater.

CAUtION: Never use a wire, needle, or similar object

to clean pilot. This can damage pilot unit.

POSSIBLE CAUSE

1. No gas supply, or shutoff valve is OFF

2. Air in gas line

3. Construction debris clogging pilot orifice

4. Low gas pressure

5. Kinked pilot line

6. Control valve knob is not opening

7. No power to unit or the ignition module

or power transformer is bad

8. Vent damper not fully open

1. Loose wiring on ignitor wire to ignition

module and/or poor ground to ignition

module

2. Pilot flame too low to sense

1. Wall switch wires defective or too long

1. Pilot flame may be too low, causing

safety pilot to “drop out”

2. Improper venting or excessive blockage

REMEDY

1. Check to see if you have gas supply and

that equipment shutoff valve is opened

2. Repeat lighting procedure several times

to purge all air out of lines. If after re-

peated attempts appliance does not light,

call for qualified service and repair.

3. Remove debris and dirt, inspect and

clean any other possible obstructions

4. Contact your gas supplier to check

pressure

5. Have a qualified technician replace pilot

line

6. Replace control valve (Refer to Replace-

ment Parts, page 27)

7. Check that main power is on and that

all wire connections are made correctly

to the ignition model (see Wiring Dia-

gram, page 21). Check for 24 VAC at the

secondary side of the transformer. If 24

VAC is present, and the module does not

operate, have the module replaced oth-

erwise have the transformer replaced.

8. Open vent damper until fully locked in

OPEN position

1. Check wiring connection. Refer to Wir-

ing Diagram, page 21, and/or check

ground wire to ignition module

2. Clean and adjust pilot burner and check

gas supply and inlet pressure to unit

Note: Have a qualified technician replace

pilot assembly if broken or corroded

1. Check electrical connections

1. Clean and adjust pilot flame for maximum

flame impingement on thermopile

2. Have the vent system inspected, includ-

ing the termination cap. Remove any

restriction or obstruction

ObSERVED PRObLEM

Ignitor will not spark or pilot will not light

Pilot will not stay lit

No gas to burner, although wall switch and

valve are set to the ON position

Frequent pilot outage

Advertising