Niveo Professional NUPS22-1000U User Manual

Page 16

Advertising
background image

13

3-5. UPS Setting

There are two parameters to set up the
UPS.
Parameter 1: It’s for program
alternatives. There are 9 programs to
set up:
Parameter 2: It’s for setting
information display。


 01: Output voltage setting

Interface

Setting

For 200/208/220/230/240 VAC models, you may choose the
following output voltage:
200: presents output voltage is 200Vac

208: presents output voltage is 208Vac
220: presents output voltage is 220Vac
230: presents output voltage is 230Vac
240: presents output voltage is 240Vac

For 100/110/150/120/127 VAC models, you may choose the
following output voltage:
100: presents output voltage is 100Vac

110: presents output voltage is 110Vac
115: presents output voltage is 115Vac
120: presents output voltage is 120Vac

127: presents output voltage is 127Vac

 02: Frequency Converter enable/disable

Interface

Setting

CF ENA: converter mode enable
CF DIS: converter mode disable

 03: Output frequency setting

Interface

Setting

You may set the initial frequency on battery mode:

BAT 50: presents output frequency is 50Hz
BAT 60: presents output frequency is 60Hz
If converter mode enable, you may choose the following output

frequency:
CF 50: presents output frequency is 50Hz
CF 60: presents output frequency is 60Hz

Parameter 2

Parameter 1