19

Symptom

Possible cause

Remedy

Fault code is shown as 43 and The

icon

is lighting on LCD

display and alarm is continuously
sounding.

The UPS shut down

automatically because of
overload at the UPS
output.

Remove excess loads from

UPS output and restart it.

Fault code is shown as 14 and

alarm is continuously sounding.

The UPS shut down

automatically because
short circuit occurs on the
UPS output.

Check output wiring and if

connected devices are in
short circuit status.

Fault code is shown as 01, 02, 03,

04, 11, 12, 13 and 41 on LCD
display and alarm is continuously
sounding.

A UPS internal fault has

occurred. There are two
possible results:
1. The load is still supplied,
but directly from AC power

via bypass.
2. The load is no longer
supplied by power.

Contact your dealer

Battery backup time is shorter

than nominal value

Batteries are not fully

charged

Charge the batteries for at

least 5 hours and then
check capacity. If the
problem

still

persists,

consult your dealer.

Batteries defect

Contact your dealer to
replace the battery.