3-6. Operating Mode Description

Operating

mode

Description

LCD display

Rack Display

Tower Display

Online mode

When the input voltage is within
acceptable range, UPS will provide

pure and stable AC power to output.
The UPS will also charge the battery at
online mode.

ECO mode
(Efficiency
Corrective
Optimizer)

When the input voltage is within
setting range (±3%Vo max), UPS will
bypass voltage to output for energy
saving. PFC and INVERTER are still
active at this mode.

AECO mode
(Advanced
Efficiency
Corrective
Optimizer)

When the input voltage is within
setting range (±3%Vo max), UPS will
bypass voltage to output for energy
saving. PFC and INVERTER are off at
this mode.

Frequency
Converter
mode

When input frequency is within 40 Hz
to 70 Hz, the UPS can be set at a
constant output frequency, 50 Hz or
60 Hz. The UPS will still charge
battery under this mode.

Battery
mode

When the input voltage is beyond the
acceptable range or power failure and
alarm is sounding every 4 second,
UPS will backup power from battery.

Bypass
mode

When input voltage is within
acceptable range but UPS is
overload, UPS will enter bypass mode
or bypass mode can be set by front
panel. Alarm is sounding every 10
second.