1. Important Safety Warning

Please comply with all warnings and operating instructions in this manual strictly. Save this

manual properly and read carefully the following instructions before installing the unit. Do not
operate this unit before reading through all safety information and operating instructions
carefully


1-1. Transportation

 Please transport the UPS system only in the original package to protect against shock

and impact.


1-2. Preparation

 Condensation may occur if the UPS system is moved directly from cold to warm

environment. The UPS system must be absolutely dry before being installed. Please
allow at least two hours for the UPS system to acclimate the environment.

 Do not install the UPS system near water or in moist environments.
 Do not install the UPS system where it would be exposed to direct sunlight or near

heater.

 Do not block ventilation holes in the UPS housing.

1-3. Installation

 Do not connect appliances or devices which would overload the UPS system (e.g.

laser printers) to the UPS output sockets.

 Place cables in such a way that no one can step on or trip over them.
 Do not connect domestic appliances such as hair dryers to UPS output sockets.
 The UPS can be operated by any individuals with no previous experience.
 Connect the UPS system only to an earthed shockproof outlet which must be easily

accessible and close to the UPS system.

 Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your

computer) to connect the UPS system to the building wiring outlet (shockproof
outlet).

 Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS

system.

 When installing the equipment, it should ensure that the sum of the leakage current

of the UPS and the connected devices does not exceed 3.5mA.

1-4. Operation

 Do not disconnect the mains cable on the UPS system or the building wiring outlet

(shockproof socket outlet) during operations since this would cancel the protective
earth of the UPS system and of all connected loads.

 The UPS system features its own, internal current source (batteries). The UPS output

sockets or output terminals block may be electrically live even if the UPS system is not
connected to the building wiring outlet.

 In order to fully disconnect the UPS system, first press the OFF/Enter button to

disconnect the mains.

 Prevent no fluids or other foreign objects from inside of the UPS system.