15

 08: Programmable outlets setting

Interface

Setting

0-999: setting the backup time limits in minutes from 0-999 for

programmable outlets which connect to non-critical devices on
battery mode.

 09: LCD display direction setting

Interface

Setting

RAC: the LCD display is horizontal.
TOE: the LCD display is vertical.

 10: Acceptable input voltage range setting

Interface

Setting

For 200/208/220/230/240 VAC models, you may choose the
following Acceptable input voltage range:
110/300 alternating flashing: acceptable input voltage range is

from 110V to 300V.
160/260 alternating flashing: acceptable input voltage range is
160V to 260V.

170/270 alternating flashing: acceptable input voltage range is
170V to 270V.
For 100/110/150/120/127 VAC models, you may choose the

following Acceptable input voltage range:
55/150 alternating flashing: acceptable input voltage range is
from 55V to 150V.
80/130 alternating flashing: acceptable input voltage range is 80V

to 130V.
85/135 alternating flashing: acceptable input voltage range is 85V
to 135V.

 00: Exit setting