Troubleshooting – Orion System Two Condenser Head Pressure II Module User Manual

Page 12

Advertising
background image

Zone

Zone

TROUBLESHOOTING

Two Condenser Head Pressure II Module Technical Guide

12

Head Pressure Module Valve / Fan Position Troubleshooting

Head Pressure Module Valve/Fan

Position Troubleshooting

If confi gured for Water valve:

Aout Signal is 2 to 10 volts.

2 volts = 0% valve position or fully closed

10 volts = 100% valve position or fully open

PWM signal is not used for water valve but does modulate.

At Startup for cooling, valve will open to 75% or 8 volts for 3
minutes then will modulate to try to maintain head pressure
setpoint.

For heating, valve will open and stay at 100%.

If confi gured for Air Condenser Fan:

Aout Signal is 0 to 10 volts.

Minimum fan speed is 1 volt. (10%)

Maximum fan speed is 10 volts. (100%)

Anything less than 1.5 volts the fan will be off.

PWM signal is 0 to 100%

PWM+ (to ground) will always read 24 vdc.

PWM- (to ground) can be measured for volts dc and this
formula will tell you the percentage signal: (24 – measured
value)/24 (measured value = PWM- to ground)

PWM-

0 volts = 100% fan speed

6 volts = 75% fan speed

12 volts = 50% fan speed

18 volts = 25% fan speed

20.4 volts = 15% fan speed

Above 20.4 volts = 0% fan speed

At Startup for cooling, fan will start at 100% for 3 minutes
and then will modulate to try to maintain head pressure
setpoint.

For heating, fan will run and stay at 100%.

Safeties:

If the head pressure signal is above 500 PSIG, fan will go to
100% (high pressure safety).


If the head pressure signal is below 1 PSIG, fan will go to
100% (assuming bad sensor).

If the head pressure rises 50 PSI above setpoint, the condenser
signal will go to 100%.