Sequence of operation, Stand-alone input commands – Orion System Two Condenser Head Pressure II Module User Manual

Page 8

Advertising
background image

Zone

Zone

SEQUENCE OF OPERATION

Two Condenser Head Pressure II Module Technical Guide

8

Stand-Alone Input Commands

Table 1: Two Condenser Head Pressure II Module
Inputs & Outputs

General

The following inputs and outputs are available on the Two Condenser
Head Pressure II Module. See Table 1 below to reference the Input/
Output Map.

Stand-Alone Input Commands

Condenser Fan A On/Off

A 24 volt signal to Binary Input #1 initiates the Condenser Fan A Enable
function. Typically, the source for this signal is the “Y” call from the
thermostat calling for a compressor to run.

Reversing Valve On/Off

A 24 volt signal to Binary Input #2 indicates the reversing valve has
been energized and initiates the Reversing Valve Enable On indication
function. Typically, the source for this signal is the “O” call from a
thermostat or other controller.

Condenser Fan B On/Off

A 24 volt signal to Binary Input #3 initiates the Condenser Fan B Enable
function. Typically, the source for this signal is the “Y” call from the
thermostat calling for a compressor to run.

Head Pressure Setpoint

The Head Pressure Setpoint is set using the OPTIONS Dip Switches. See
Table 2. The Default Setpoint for an Air Cooled Condenser is 340 for
410-A refrigerant. The Default Setpoint for a Water Cooled Condenser
is 235 for 410-A refrigerant. Set the OPTIONS Dip Switch to 0 if using
these Default Settings. See “ADDRESS Dip Switch” below. You must
cycle power after setting Dip Switch values.

NOTE: The only setpoint available for adjustment by the con-

tractor is the Head Pressure Setpoint. The rest of the
setpoints described can only be changed by the factory.

ADDRESS Dip Switch Settings for Condenser

Type Selection

When using the OPTIONS Dip Switch to set the Head Pressure Setpoint,
you must also set the ADDRESS Dip Switch to designate the type of
condenser you are using.

Set ADDRESS Dip Switch 1 to ON for a Water Cooled Condenser or
to OFF for an Air Cooled Condenser.

If set to ON for a Water Cooled Condenser, the Analog Condenser Output
Signal will be 2-10 VDC for the Water Valve. If set to OFF for an Air
Cooled Condenser, the Analog Condenser Output Signal will be 0-10
VDC for the Condenser Fan.

You must cycle power after setting Dip Switch values. See Figure
3 or 4
for ADDRESS Dip Switch location and Table 3 for Setting
information.

Binary Inputs

1

Condenser Fan A On/Off (24 VAC Wet Input)

2

Reversing Valve On/Off (24 VAC Wet Input)

3

Condenser Fan B On/Off (24 VAC Wet Input)

Binary Outputs

1

Condenser A Enable Relay
(Dry Contact Output Rated for 24 VAC)

2

Reversing Valve A Enable
(Dry Contact Output Rated for 24 VAC)

3

Condenser B Enable Relay
(Dry Contact Output Rated for 24 VAC)

4

Reversing Valve B Enable
(Dry Contact Output Rated for 24 VAC)

Analog Inputs

1

Head Pressure #1 (0-667 PSI Sensor)

2

Head Pressure #2 (0-667 PSI Sensor)

3

Head Pressure #3 (0-667 PSI Sensor)

4

Head Pressure #4 (0-667 PSI Sensor)

Analog Outputs (0-10 or 2-10 VDC)

1

Condenser Signal A (AOUT 1)

2

Condenser Signal B (AOUT 2)

PWM Inputs

1

ECM 142 PWM Input (0-100% Duty Cycle)

2

ECM 142 PWM Input (0-100% Duty Cycle)

Advertising