INSTALLATION & WIRING

Two Condenser Head Pressure II Module Technical Guide

4

Mounting and Wiring Considerations

Environmental Requirements

The Two Condenser Head Pressure II Module needs to be installed in
an environment that can maintain a temperature range between -30°F
and 150°F and not exceed 90% RH levels (non-condensing).

Mounting

The Two Condenser Head Pressure II Module is housed in a plastic
enclosure. It is designed to be mounted by using the 3 mounting holes
in the enclosure base. It is important to mount the module in a location
that is free from extreme high or low temperatures, moisture, dust, and
dirt. Be careful not to damage the electronic components when mount-
ing the module.

See Figure 2 for Module dimensions (in inches).

LED BLINK CODES

LED NAME

STAT

BLINKS QTY. OF SENSORS INSTALLED

LED NAME

ALARM

NO PROBLEMS

0

NO SENSORS DETECTED

1

HIGH HEAD PRESSURE DETECTED

2

LOW HEAD PRESSURE DETECTED

3

WattMaster Label

#LB102110-A

Rev.: 1A

E-BUS

Connector

E-BUS

Connector

+5V

SIG 1

GND

+5V

SIG 2

GND

+5V

SIG 3

GND

+5V

SIG 4

GND

+24

VAC

GND

BIN 1

BIN 2

BIN 3

COM

HEAD
PRESSURE
TRANSDUCER #1

HEAD
PRESSURE
TRANSDUCER #2

HEAD
PRESSURE
TRANSDUCER #3

HEAD
PRESSURE
TRANSDUCER #4

REV. VLV. ENABLE INPUT

COMMON

PWM2+

AAON No.:

V20660

AO1

AO2

GND

COND. A ENABLE INPUT

COND. B ENABLE INPUT

COND. A SIGNAL
COND. B SIGNAL

PWM1-

PWM1+

PWM2-

COND. FAN A

COND. FAN B

COND. FAN A

COND. FAN B

GND

Two Condenser Head Pressure II Module

2C2

Orion No.:OE370-23-HP

www.aaon.com

RELA

Y

C

ONT

A

CT

RA

TING

IS

1

A

MP

MAX

@

24

V

A

C

COND. A ENABLE

COND. B ENABLE

REV. VLV. A ENABLE

REV. VLV. B ENABLE

R1

R2

R3

R4

RC

RELAY COMMON

A1

A2

B1

B2

5.04

5.64

5.71

2.07

0.55

4.14

0.29

0.18 DIA. TYP.

ALARM

ANALOG

STAT

COMM

R1

R2

GND

RELAYS

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

ADDRESS

OPTIONS

+5V

SIG 2

GND

+5V

SIG 3

GND

+5V

SIG 4

GND

+5V

SIG 1

GND

BIN 1

BIN 2

BIN 3

COM

Figure 2: Two Condenser Head Pressure II Module Dimensions

Important Wiring Considerations

Please read carefully and apply the following information when wiring
the Two Condenser Head Pressure II Module:

1. To operate the Two Condenser Head Pressure II Module, you

must connect power to the 24 VAC input terminal block.

2. Each Pressure Transducer must have its own 18-gauge

shielded twisted pair cable. The Drain Wire must be the “Gnd”
signal for the transducer.

3. When the Analog Output is being used to control the

Condenser Fan Speed or Water Valve Percentage, the cable
must be 18-gauge shielded wire, and the Drain Wire must be
the “Gnd” signal.

4. If the Pulse Width Modulation (PWM) Output is being used to

directly control the ECM 142 motor, the wires do not need to
be shielded and can be any 18-gauge wire.