Two Condenser Head Pressure II Module Technical Guide

INSTALLATION & WIRING

3

Overview

The Two Condenser Head Pressure II Module (OE370-23-HP2C2)
monitors four individual head pressure transducers and controls two
Condenser Fans or Water Valves on units with two physically separate
condenser sections. The highest reading of head pressure transducers 1
& 2 controls Condenser Signal A. The highest reading of head pressure
transducers 3 & 4 controls Condenser Signal B. If this is a heat pump unit,
the module is able to detect when the unit is in Heat Pump Heating mode
and will force the condenser signal to 100% until it leaves this mode.

The Two Condenser Head Pressure II Module is designed to work
stand-alone by using its OPTIONS dip switch to adjust the Head Pres-
sure setpoint.

The Two Condenser Head Pressure II Module is directly connected to
the VCM-X Modular E-BUS, VCM-X WSHP E-BUS or SA E-BUS
Controller, allowing the Module(s) to receive setpoints from the Con-
troller. See chart on page 2 for part numbers.

When using the Two Condenser Head Pressure II Module with the RNE
Controller, refer to the RNE Controller Technical Guide.

The Two Condenser Head Pressure II Module also provides a pulse
width modulation (PWM) signal or voltage output signal to control the
condenser fans.

The Two Condenser Head Pressure II Module requires a 24 VAC power
connection with an appropriate VA rating.

Module Overview

Figure 1: Two Condenser Head Pressure II Module

Features

The Two Condenser Head Pressure II Module provides the following:



Can be operated stand alone or up to (2) modules can be

daisy-chained together and connected to a VCM-X

Modular E-BUS, VCM-X WSHP E-BUS, or SA E-BUS

Controller



Monitors up to four individual head pressure transducers



Provides control of Condenser Output Signals based on the

highest reading of head pressure transducers



Capable of monitoring a Reverse Valve Signal



Forces Condenser Fans to 100% while in the Heat Pump

Heating

Mode

NOTE: The Two Condenser Head Pressure II Module contains

no user-serviceable parts. Contact qualifi ed technical
personnel if your Module is not operating correctly.

ALARM

ANALOG

STAT

COMM

R1

R2

GND

RELAYS

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

ADDRESS

OPTIONS

+5V

SIG 2

GND

+5V

SIG 3

GND

+5V

SIG 4

GND

+5V

SIG 1

GND

BIN 1

BIN 2

BIN 3

COM

LED BLINK CODES

LED NAME

STAT

BLINKS QTY. OF SENSORS INSTALLED

LED NAME

ALARM

NO PROBLEMS

0

NO SENSORS DETECTED

1

HIGH HEAD PRESSURE DETECTED

2

LOW HEAD PRESSURE DETECTED

3

WattMaster Label

#LB102110-A

Rev.: 1A

E-BUS

Connector

E-BUS

Connector

+5V

SIG 1

GND

+5V

SIG 2

GND

+5V

SIG 3

GND

+5V

SIG 4

GND

+24

VAC

GND

BIN 1

BIN 2

BIN 3

COM

HEAD
PRESSURE
TRANSDUCER #1

HEAD
PRESSURE
TRANSDUCER #2

HEAD
PRESSURE
TRANSDUCER #3

HEAD
PRESSURE
TRANSDUCER #4

REV. VLV. ENABLE INPUT

COMMON

PWM2+

AAON No.:

V20660

AO1

AO2

GND

COND. A ENABLE INPUT

COND. B ENABLE INPUT

COND. A SIGNAL

COND. B SIGNAL

PWM1-

PWM1+

PWM2-

COND. FAN A

COND. FAN B

COND. FAN A

COND. FAN B

GND

Two Condenser Head Pressure II Module

2C2

Orion No.:OE370-23-HP

www.aaon.com

RELA

Y

C

ONT

A

CT

RA

TING

IS

1

A

MP

MAX

@

24

V

A

C

COND. A ENABLE

COND. B ENABLE

REV. VLV. A ENABLE

REV. VLV. B ENABLE

R1

R2

R3

R4

RC

RELAY COMMON

A1

A2

B1

B2