INSTALLATION & WIRING

Two Condenser Head Pressure II Module Technical Guide

6

E-BUS Controller to Two Condenser Head Pressure II Module Wiring

VCM-X Modular E-BUS, VCM-X WSHP

E-BUS or SA E-BUS Controller to Two

Condenser Head Pressure II Module

Wiring

Up to (2) Two Condenser Head Pressure II Modules can be daisy-chained
together and connected to the E-BUS Controller using a modular HSSC
cable. The Two Condenser Head Pressure II Module requires a 24 VAC
power connection with an appropriate VA rating. See Figure 4 below
for wiring.

Any E-BUS Module can be connected to the E-BUS Controller’s E-BUS
port or can be daisy-chained together using HSSC cables.

NOTE: Contact Factory for the correct HSSC cable length for

your application. Cables are available in ¼, ½, 1, 2, 3,
4, and 5 Meter lengths and 100 and 150 Foot lengths.

Figure 4: VCM-X E-BUS Controller to Two Condenser Head Pressure II Module Wiring Diagram

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

Head Pressure Transducers

0 - 667 PSI

(One Per Refrigerant Circuit)

OE370-23-HP2C2

Two Condenser Head Pressure II Module

OPTIONS Dip Switch Setting Not Required

When Connected To

VCM-X E-BUS Controller

or SA E-BUS Controller

+5V

SIG 2

GND

OP

T

IO

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

R1

R2

GND

RELAYS

SIG 3

+5V

GND

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

PWR

Connect To Other

WattMaster-Approved

E-BUS Expansion Module(s)

HSSC Cable

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!! Observe Polarity! All boards
must be wired with GND-to-GND and 24
VAC-to-24 VAC.
Failure to observe polarity could result in
damage to the boards.

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY - 1 AMP MAXIMUM LOAD

ALL RELAY OUTPUTS

ARE

HSSC Cable

Connect To VCM-X E-BUS

Controller or SA E-BUS Controller

Set ADDRESS Dip Switch 1 to ON for

Water Cooled or to OFF for Air Cooled.

Currently showing OFF for Air Cooled.

Set ADDRESS Dip Switch 2 to OFF

on all communicating applications

unless it is intended to be the Second

Head Pressure Module on a system. If

set to ON, it will not communicate.

Set ADDRESS Dip Switch 3 to ON to

disable Circuit B alarms when only one

Condenser is Used. Currently showing

OFF.

Set ADDRESS Dip Switch 4 to OFF to

make reversing valve "ON to Heat /

OFF to Cool.” Set to ON to make

reversing valve “ON to Cool / OFF to

Heat.” Currently showing OFF.

.

Currently showing OFF.

ADDRESS

BIN 1

BIN 2

BIN 3

COM

+24 Volts

Condenser Fan A

ECM Motor

Duty Cycle

Condenser Fan B

ECM Motor

COM

+

Condenser

Signal B

COM

+

Condenser

Signal A

CONDENSER A ENABLE

R1

HVAC UNIT CONNECTION

R3

CONDENSER B ENABLE

COMM

REVERSING VALVE B ENABLE

REVERSING VALVE A ENABLE

R4

R2

YELLOW

BLUE +24 OUT

+24 Volts

Duty Cycle

YELLOW

BLUE +24 OUT

LED BLINK CODES

LED NAME

STAT

BLINKS QTY. OF SENSORS INSTALLED

LED NAME

ALARM

NO PROBLEMS

0

NO SENSORS DETECTED

1

HIGH HEAD PRESSURE DETECTED

2

LOW HEAD PRESSURE DETECTED

3

WattMaster Label

#LB102110-A

Rev.: 1A

E-BUS

Connector

E-BUS

Connector

+5V

SIG 1

GND

+5V

SIG 2

GND

+5V

SIG 3

GND

+5V

SIG 4

GND

+24

VAC

GND

BIN 1

BIN 2

BIN 3

COM

HEAD
PRESSURE
TRANSDUCER #1

HEAD
PRESSURE
TRANSDUCER #2

HEAD
PRESSURE
TRANSDUCER #3

HEAD
PRESSURE
TRANSDUCER #4

REV. VLV. ENABLE INPUT

COMMON

PWM2+

AAON No.:

V20660

AO1

AO2

GND

COND. A ENABLE INPUT

COND. B ENABLE INPUT

COND. A SIGNAL
COND. B SIGNAL

PWM1-

PWM1+

PWM2-

COND. FAN A

COND. FAN B

COND. FAN A

COND. FAN B

GND

Two Condenser Head Pressure II Module

2C2

Orion No.:OE370-23-HP

www.aaon.com

RELA

Y

C

ONT

A

CT

RA

TING

IS

1

A

MP

MAX

@

24

V

A

C

COND. A ENABLE

COND. B ENABLE

REV. VLV. A ENABLE

REV. VLV. B ENABLE

R1

R2

R3

R4

RC

RELAY COMMON

A1

A2

B1

B2