Technical Guide

Water Source Heat Pump Module

11

Sequence of Operation

Table 2: Water Source Heat Pump Module Inputs &
Outputs

General

The following inputs and outputs are available on the Water Source Heat
Pump Module. See Table 2 below to reference the Input/Output Map.

Binary Inputs

1

Circuit A, 1

st

Compressor Enable (BIN 1)

2

Circuit A, 2

nd

Compressor Enable (BIN 2)

3

Circuit B, 1

st

Compressor Enable (BIN 3)

4

Circuit B, 2

nd

Compressor Enable (BIN 4)

5

Cool Enable (BIN 5)

6

Water Proof of Flow (BIN 6)

Analog Inputs

1

Suction Pressure Circuit A (Pres 1)

2

Not Used

3

Suction Pressure Circuit B (Pres 3)

4

Not Used

5

Leaving Water Temperature (T1)

Analog Outputs (1-5 VDC)

1

Circuit A - Digital Compressor A1 (AOUT1)

2

Circuit B - Digital Compressor B1 (AOUT2)

NOTE: Analog Outputs are not used on Stand Alone
Application

Relay Outputs (24 VAC)

1

Circuit A, 1

st

Compressor Enable Output (RLY1)

2

Circuit A, 2

nd

Compressor Enable Output (RLY2)

3

Circuit B, 1

st

Compressor Enable Output (RLY3)

4

Circuit B, 2

nd

Compressor Enable Output (RLY4)

5

Alarm Output (RLY5)

Table 3: Factory-Set Default Setpoints - Water Only

Default Setpoints

Description

Setpoint

UNSAFE SUCTION

40 PSIG

LOW SUCTION HEAT MODE

100 PSIG

LOW SUCTION COOL MODE

100 PSIG

LOW LEAVING WATER TEMP

37ºF

Water Source Heat Pump Module

Setpoints

The Water Source Heat Pump Module setpoints are preset at AAON
and are based on the unit’s design and type of coolant being used in the
water loop. See Tables 3 & 4 for default settings.

NOTE: These are default settings only. The setpoints may be

different based on the unit’s design and type of coolant
being used. For fi eld adjustment of these setpoints, you
must contact the AAON factory.

Glycol Default Setpoints

Description

20% Glycol 40% Glycol

UNSAFE SUCTION

40 PSIG

40 PSIG

LOW SUCTION HEAT MODE

77 PSIG

45 PSIG

LOW SUCTION COOL MODE

85 PSIG

85 PSIG

LOW LEAVING WATER TEMP

23ºF

0ºF

Table 4: Factory-Set Default Setpoints - Glycol