Water source heat pump module, Installation & wiring, Technical guide – Orion System Water Source Heat Pump Module User Manual

Page 9

Advertising
background image

Technical Guide

Water Source Heat Pump Module

9

Installation & Wiring

Figure 4, cont.: VCM-X WSHP Controller to Water Source Heat Pump Module Wiring Diagram

WATTMASTER CONTROLS

Y 102374 REV 0

S

MADE IN USA

WARNING!!
Observe Polarity! All boards must
be wired with GND-to-GND and
24 VAC-to-24 VAC. Failure to
observe polarity could result in

OE365-23-EBD E-BUS

Distribution Module

GND

-COMM

SHLD

+COMM

INPUT

+COMM

SHLD

-COMM

GND

+VDC

485 DRV

24VAC

GND

PWR

YS102308
REV 1
I2C TO COMM
DIST. BOARD

OUTPUT

Modular Cable

Connect To

VCM-X WSHP Controller

Set Address to 1

When Using One

WSHP Module And

Set Addresses

Consecutively if

Using More Than

One. Note: Address

Zero Defaults To

Address 1.

OE334-23-WPM-C Water Source

Heat Pump Module

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY

ALL RELAY OUTPUTS

ARE

COMP. A2 ENABLE

COMP. A1 ENABLE

R1

R4
R5

R3

R2

COMM

COMP. B1 ENABLE
COMP. B2 ENABLE

ALARM OUTPUT

HVAC UNIT
CONNECTIONS

HSSC Cable

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

Connect To Other

WattMaster-Approved

E-BUS Expansion

Module(s)

WARNING!!
Observe Polarity! All
boards must be wired
with GND-to-GND and
24 VAC-to-24 VAC.
Failure to observe
polarity could result in
damage to the boards.

HSSC Cable

DIGITAL STAGE 1 (1.5-5V)

AO1
AO2

DIGITAL STAGE 2 (1.5-5V)

GND

T1

CIRCUIT A

SUCTION PRESSURE TRANSDUCER

BK

RD

WH

WATER POF
CONTACT

BIN6

COM

LEAVING WATER TEMPERATURE

CIRCUIT B

SUCTION PRESSURE TRANSDUCER

BK

RD

WH

E

WattMaster Label

#LB102069-B

Rev.: 1E

E-BUS

Connector

E-BUS

Connector

+24

VAC

GND

WSHP Module

Orion No.: OE334-23-WPM-C

AAON Coil No.: 30318

www.aaon.com

www.orioncontrols.com

RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC

COMP. A2 ENABLE

COMP. A1 ENABLE

R1

R2

R3

R4

R5
RC

RELAY COMMON

COMP. B1 ENABLE

COMP. B2 ENABLE

ALARM OUTPUT

+5V

PRES

GND

+5V

PRES

GND

BIN 1

BIN 2

BIN 3

BIN 4

BIN 5

BIN 6

BIN 7

COM

SUCT. PR. SENSOR
PRES 1=A1, PRES 2=N/A
PRES 3=B1, PRES 4=N/A

NOT USED
PRES 1=A1, PRES 2=N/A
PRES 3=B1, PRES 4=N/A

COMP. A1 ENABLE
COMP. A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
COOL ENABLE
WATER POF
NOT USED
COMMON

T 1

T 2

GND

LEAVING WATER TEMP

GROUND

NOT USED

LED BLINK CODES

LED NAME

STATUS

OFF MODE

1

COOLING MODE

2

HEATING MODE

3

LED NAME

ALARM

LOW SUCTION PRESSURE

1

COMPRESSOR LOCKOUT

2

WATER FLOW FAILURE

3

LOW LEAVING WATER TEMP.

4

LED NAME

PRES 1-4

SENSOR DETECTED

ON

NO SENSOR DETECTED

OFF

LOW SUCTION PRESSURE

1

COMPRESSOR LOCKOUT

2

AO1

A2O

CIRCUIT A -COMP. A1

+5 NOT USED, PRES TO P6 & GND TO P5

+5 TO RED, PRES TO WHT & GND TO BLK

CONNECT TO CNTLR C2 TERM.

CIRCUIT B - COMP. B1

DIGITAL COMRESSORS

DIGITAL COMP. A1 & B1

NON-DIGITAL COMPRESSORS

Advertising