The Water Source Heat Pump Module monitors the compressors on an
AAON

®

Water Source Heat Pump unit and can disable the compres-

sors based on low Suction Pressure, Leaving Water Temperature, and
Water Proof of Flow inputs. It also utilizes a Delay Timer to prevent the
compressors from turning on at the same time.

There is one water-only version of the Water Source Heat Pump Mod-
ule—the OE334-23-WPM-C which uses R-410A refrigerant.

There are also two 410-A glycol versions—the OE334-23-WPM-C20
which uses 20% glycol and the OE334-23-WPM-C40 which uses 40%
glycol.

The Water Source Heat Pump Module can be used stand-alone. It can
also be connected to the VCM-X WSHP Controller (OE332-23-VCMX-
WSHP-C) using the E-BUS Distribution Module (OE365-23-EBD-C).
This allows the Water Source Heat Pump Module to receive control data
and alarms from the VCM-X WSHP Controller.

The Water Source Heat Pump Module requires a 24 VAC power con-
nection with an appropriate VA rating.

Module Overview

Figure 1: Water Source Heat Pump Module

Features

The Water Source Heat Pump Module provides the following:



Can be operated stand-alone or connected to a

VCM-X WSHP Controller using the E-BUS

Distribution Module to E-BUS interface



Capable of controlling digital compressors when

connected to the VCM-X WSHP Controller



Monitors suction pressure, leaving water

temperature, and water proof of fl ow



Provides Delay Timer to prevent compressors

from turning on at the same time

NOTE: The Water Source Heat Pump Module contains no user-

serviceable parts. Contact qualifi ed technical personnel
if your Module is not operating correctly.

WATTMASTER CONTROLS

Y 102374 REV 0

S

MADE IN USA

WattMaster Label

#LB102069-B

Rev.: 1E

E-BUS

Connector

E-BUS

Connector

+24

VAC

GND

WSHP Module

Orion No.: OE334-23-WPM-C

AAON Coil No.: 30318

www.aaon.com

www.orioncontrols.com

RELAY CONTACT RATING
IS 1 AMP MAX @ 24 VAC

COMP. A2 ENABLE

COMP. A1 ENABLE

R1

R2

R3

R4

R5
RC

RELAY COMMON

COMP. B1 ENABLE

COMP. B2 ENABLE

ALARM OUTPUT

+5V

PRES

GND

+5V

PRES

GND

BIN 1

BIN 2

BIN 3

BIN 4

BIN 5

BIN 6

BIN 7

COM

SUCT. PR. SENSOR
PRES 1=A1, PRES 2=N/A
PRES 3=B1, PRES 4=N/A

NOT USED
PRES 1=A1, PRES 2=N/A
PRES 3=B1, PRES 4=N/A

COMP. A1 ENABLE
COMP. A2 ENABLE
COMP. B1 ENABLE
COMP. B2 ENABLE
COOL ENABLE
WATER POF
NOT USED
COMMON

T 1

T 2

GND

LEAVING WATER TEMP

GROUND

NOT USED

LED BLINK CODES

LED NAME

STATUS

OFF MODE

1

COOLING MODE

2

HEATING MODE

3

LED NAME

ALARM

LOW SUCTION PRESSURE

1

COMPRESSOR LOCKOUT

2

WATER FLOW FAILURE

3

LOW LEAVING WATER TEMP.

4

LED NAME

PRES 1-4

SENSOR DETECTED

ON

NO SENSOR DETECTED

OFF

LOW SUCTION PRESSURE

1

COMPRESSOR LOCKOUT

2

AO1

A2O

CIRCUIT A -COMP. A1

+5 NOT USED, PRES TO P6 & GND TO P5

+5 TO RED, PRES TO WHT & GND TO BLK

CONNECT TO CNTLR C2 TERM.

CIRCUIT B - COMP. B1

DIGITAL COMRESSORS

DIGITAL COMP. A1 & B1

NON-DIGITAL COMPRESSORS

Advertising