Water source heat pump module, Sequence of operation, Technical guide 12 – Orion System Water Source Heat Pump Module User Manual

Page 12: Stand-alone input commands, Input commands (vcm-x wshp )

Advertising
background image

Water Source Heat Pump Module

Technical Guide

12

Sequence of Operation

Stand-Alone Input Commands

Compressor On/Off

A 24 volt signal to Binary Inputs #1-4 initiates each Compressor’s On
function. The source for this signal would typically come from Y1 to
Y4 calls from the thermostat.

Cool Enable On/Off

A 24 volt signal on this input indicates the unit is in the Cooling Mode.
Typically, the source for this signal is the “O” call from the thermo-
stat.

Water Proof of Flow Circuit On/Off

A 24 volt signal to Binary Input #6 indicates Water Proof of Flow for
each circuit.

Suction Pressure Analog Inputs

Sensors from Analog Inputs #1 & #3 correlate with the Suction Pres-
sure of each Circuit (250 PSI). Pres 1 input correlates with Circuit A’s
1

st

and 2

nd

compressor. Pres 3 input correlates with Circuit B’s 1

st

and

2

nd

compressor. Suction Pressure Transducer is 0-250 psi.

Leaving Water Temperature Thermistor Inputs

T1 for Heating Mode measures the temperature of the leaving water to
prevent freezing of the coil.

Input Commands (VCM-X WSHP )

NOTE: When the term “ON” is used, it means there is either 24

VAC on the appropriate Binary Input or a call-to-run
signal is being received from the VCM-X WSHP. When
the term “OFF” is used, it means there is either 0 VAC
on the appropriate Binary Input or the call-to-run signal
from the VCM-X WSHP has been removed.

Compressor On/Off

Instead of a physical input signaling the Compressor On/Off function,
the VCM-X WSHP Controller communications drives the Compressor
On/Off function.

Cool Enable On/Off

As with the Compressor On/Off function, the VCM-X Controller
communicates to the Module that it is in Heat Mode. On = Cool. Off
= Heat.

Advertising