Installation & wiring, Water side economizer wiring – Orion System SA Controller User Manual

Page 17

Advertising
background image

SA Controller Technical Guide

Installation & Wiring

17

Water Side Economizer Wiring

Water Side Economizer (WSE) Valve(s)

The Water Side Economizer Valve(s) must be wired as shown in Figure
12
below for proper operation of the SA Controller. The Water Side
Economizer Valve(s) connects to AO1 on the SA Controller.

NOTE: For Dual Cabinet Units, wire the Second Cabinet’s WSE
Valve Actuator in parallel with the First Cabinet’s WSE Valve
Actuator.

Figure 12: Water Side Economizer Valve Wiring

Figure 13: Water Side Economizer Bypass Valve Wiring

Water Side Economizer (WSE) Bypass

Valve

The Water Side Economizer Bypass Valve(s) must be wired as shown in
Figure 13 below for proper operation of the SA Controller. The Water
Side Economizer Bypass Valve(s) are wired to AO4 and AO5 on the
SA Expansion Module.

NOTE: For Dual Cabinet Units, wire the Second Cabinet’s WSE
Bypass Valve Actuator to AO5 on the SA Expansion Module.

Advertising