Installation & wiring, Sa expansion module input wiring, Sa controller technical guide 20 – Orion System SA Controller User Manual

Page 20: Sa expansion module, Zone

Advertising
background image

Zone

Zone

Installation & Wiring

SA Controller Technical Guide

20

SA Expansion Module Input Wiring

Figure 16: OE333-23-SA – SA Expansion Module Input Wiring

SA Expansion Module

Two different Expansion Modules are available for use with the SA
Controller to provide additional inputs and outputs beyond those found
on the SA Controller.

The SA Expansion Module ( OE333-23-SA Controller) provides 8 Binary
Inputs, 4 Analog Inputs, 5 Analog Outputs, and 4 Confi gurable Relay
Outputs. See Figures 16 and 17 for complete wiring details.

Emergency Shutdown - N.C. Input

Drain Pan Overflow A - N.O. Input

Drain Pan Overflow B - N.O. Input

Water Proof of Flow B - N.O. Input

Air Proof Of Flow - N.O. Input

Remote Forced Occupied - N.O. Input

VOUT (0-5V)

0-5V

GND

GND

VIN

VAC OR DC

Water Proof of Flow A - N.O. Input

Dirty Filter - N.O. Input

AI2

AI3

AI4

B 7

I

B 6

I

B 5

I

B 3

I

B 4

I

B 1

I

B 2

I

Modular Cable

Connect To SA Controller

Modular Cable

Connect To E-BUS Distribution

Module (When Used)

24 VAC

GND

Entering Air

Humidity Sensor

Indoor Air

Humidity Sensor

10 VA Minimum Power Required

For SA Expansion Module

WARNING!!

Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity
will result in damage to one or more of the boards. Expansion Module must be wired in such a way that the
expansion module and the controller are always powered together. Loss of power to the expansion module will
cause the controller to become inoperative until power is restored to the expansion module.

SA Expansion Module

AI1

GND

GND

BI8

SA

See Humidity Sensor Wiring
Details For Complete Wiring
Information.

See Suction Pressure
Transducer Wiring Details For
Complete Wiring Information.

Additional Suction
Pressure Sensor Required
On Dual Units Only.

RD

RD

WH

WH

BK

BK

Suction Pressure

Transducer #1

Suction Pressure

Transducer #2

Splice Wire As Required To Reach
From Transducer Location To
Expansion Module Location

The 12-Relay Expansion Module ( OE358-23-12R) provides for 12
Dry Contact Confi gurable Relay Outputs. See Figure 25 for complete
wiring details.

The expansion modules can be used individually or together to provide
the required inputs and outputs for your specifi c applications.

Revised 6/21/11