SA Controller Technical Guide

Installation & Wiring

23

SA Expansion Module Binary Inputs

The SA Expansion Module provides 8 Binary Inputs. See Figure 19
below for detailed wiring.

The transformer used for powering the SA Expansion Module must also
be used to power the binary inputs.

Figure 19: OE333-23-SA – SA Expansion Module 8 Binary Inputs Wiring

Warning: Do not apply any voltage greater than 24 VAC to the
binary inputs. Higher voltages will damage the expansion module
and possibly other components on the system.

BI8

BI7

BI6

BI5

BI3

BI4

BI1

BI2

Modular Cable

Connect To SA Controller

Modular Cable

Connect To E-BUS

Distribution Module

(When Used)

24 VAC

GND

SA Expansion Module

10 VA Minimum Power Required

For SA Expansion Module

WARNING!!

Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe
polarity will result in damage to one or more of the boards. Expansion Module must be wired in such a
way that the expansion module and the controller are always powered together. Loss of power to the
expansion module will cause the controller to become inoperative until power is restored to the
expansion module.

SA

Emergency Shutdown - N.C. Input

Drain Pan Overflow A - N.O. Input

Drain Pan Overflow B - N.O. Input

Water Proof of Flow B - N.O. Input

Air Proof Of Flow - N.O. Input

Remote Forced Occupied - N.O. Input

Water Proof of Flow A - N.O. Input

Dirty Filter - N.O. Input

SA Expansion Module Binary Inputs Wiring