Appendix B

Temperature and

Current Limits

The range of temperature, heater currents, currents and ground/earth leakage are
tabulated in the below list.

Parameters

Limits

TEMPERATURES

All circuit temperature set points for the TCM18
should be programmed with the following limits:

MinTemp <= LTA < MT <

(MT + CB) < HTA <= HTT <= MaxTemp

MinTemp

= -200

F (-128

C)

LTA

= Low Temp Alarm

MT

= Maintain Temp

CB

= Control Band

HTA

= High Temp Alarm

HTT

= High Temp Trip (or HHAlarm)

MaxTemp

= 1112

F (600

C)