Thermon TraceNet TCM 18 User Manual
Page 9

Auxiliary power output
24 Vdc at 0.5 Amps
Panel ambient operat-
ing temperature range
-40
◦
F (-40
◦
C) to 131
◦
F (55
◦
C)
Storage temperature
range
-40
◦
F (-40
◦
C) to 158
◦
F (70
◦
C)
Alarm relay outputs
Option U
3 sealed dry contact relays rated 0.4A resistive at 24 Vdc
Option A
3 sealed dry contact relays rated 0.5A resistive at 100-240
Vac
Control relay outputs
Up to eighteen DC outputs each having a sink current capa-
bility of 100 mA 12VDC (24 Vdc optional by programming)
Control options
On/Off, On/Off with Soft Start, Proportional, and Ambient
Proportional Control
LCD heated display
1-3/4” ( 44 mm) x 4.875” (124 mm)
TCM18 module
operating temperature
range
-40
◦
F (-40
◦
C) to 140
◦
F (60
◦
C)
The PM6 has the following operating specifications:
Circuit control capacity
up to six heat trace circuits
Single pole relay switching capacity
30 Amperes at 240 Vac*
Dual pole relay switching capacity
15 Amperes at 240 Vac*
Maximum power consumption
less than 3 Watts
Relay power connection
40-Pin header ribbon cable
Ground/earth leakage test connection
10-Pin header ribbon cable
Maximum storage temperature
185
◦
F (85
◦
C)
Minimum storage temperature
-40
◦
F (-40
◦
C)
Oper. ambient temp. range
-40
◦
F (-40
◦
C) to 158
◦
F (70
◦
C)
5
PN 50316_0514