background image

Auxiliary power output

24 Vdc at 0.5 Amps

Panel ambient operat-
ing temperature range

-40

F (-40

C) to 131

F (55

C)

Storage temperature
range

-40

F (-40

C) to 158

F (70

C)

Alarm relay outputs

Option U

3 sealed dry contact relays rated 0.4A resistive at 24 Vdc

Option A

3 sealed dry contact relays rated 0.5A resistive at 100-240
Vac

Control relay outputs

Up to eighteen DC outputs each having a sink current capa-
bility of 100 mA 12VDC (24 Vdc optional by programming)

Control options

On/Off, On/Off with Soft Start, Proportional, and Ambient
Proportional Control

LCD heated display

1-3/4” ( 44 mm) x 4.875” (124 mm)

TCM18 module
operating temperature
range

-40

F (-40

C) to 140

F (60

C)

The PM6 has the following operating specifications:

Circuit control capacity

up to six heat trace circuits

Single pole relay switching capacity

30 Amperes at 240 Vac*

Dual pole relay switching capacity

15 Amperes at 240 Vac*

Maximum power consumption

less than 3 Watts

Relay power connection

40-Pin header ribbon cable

Ground/earth leakage test connection

10-Pin header ribbon cable

Maximum storage temperature

185

F (85

C)

Minimum storage temperature

-40

F (-40

C)

Oper. ambient temp. range

-40

F (-40

C) to 158

F (70

C)