Thermon TraceNet TCM 18 User Manual

Page 83

Advertising
background image

Circuit Number

2

7

9

12

16

RTD Sensor Mode

1 AMB

1 AMB

2 AMB

1 AMB

2 AMB

RTD#1 Input

−10

OPEN

−14

OPEN

−8

RTD#2 Input

XX

XX

−12

XX

OPEN

RTD#1 Reading Used

a-10

−10

−14

−10

−8

RTD#2 Reading Used

XX

XX

a-12

XX

−12

Note: XX is an ignored RTD Input due to 1 AMB Mode

Note that Circuit 2 RTD#1 is reading an ambient -10, so the TCM18 uses this RTD
as the main RTD control sensor (SysAmbient1). Since this input is SysAmbient1 an
‘a’ is prepended to the reading displayed. The Circuit 2 RTD#2 is not installed so
this sensor location is ignored. Note also that on Circuit 9 both RTD#1 and RTD#2
are programmed as ambient sensed and are reading -14 and -12 respectively, so
the backup second RTD (SysAmbient2) will be RTD#2 from Circuit 9. Since this
input is SysAmbient2 an ‘a’ is prepended to the reading displayed.

Because Circuit 2 has an RTD reading within the stipulated valid range, it will con-
trol off its own RTD#1 sensor. Also Circuit 7 will control off the main RTD sensor
(SysAmbient1) since its own RTD#1 input is reading as OPEN (no sensor present).
Circuit 9 will control off its own RTD#1 and RTD#2 inputs because both are valid RTD
ambient readings. Circuit 12 will control off the main ambient RTD sensor (SysAmbi-
ent1) since its own RTD#1 sensor has an OPEN reading (no sensor present). Circuit
16 will control off its own RTD#1 sensor and the backup RTD sensor (SysAmbient2)
since its own RTD#2 sensor has an OPEN reading (sensor not present).

In this arrangement, all other circuits were programmed as pipe sensing RTD sen-
sors and thus each of those circuits ignore the ambient sensing RTD readings and
use the sensors present for those circuits.

79

PN 50316_0514

Advertising