Thermon TraceNet TCM 18 User Manual
Page 85
Advertising

HEATER
POWER
PIPE/SURFACE
TEMPERATURE
POWER
100%
20%
0%
-29
10
DEGREES CELSIUS
PIPE/SURFACE
TEMPERATURE
DEGREES
CELSIUS
20
10
0
Example D2 - Foundation Heave Protection - Proportional Control With Solid State
Relay Output
Cryogenic vessels and refrigerated rooms often utilize heating systems beneath to
prevent heaving due to the freezing of the soil/foundation base structure. A typical
heat tracing application of this type might require an operating tracing design as fol-
lows:
Internal Room Temperature:
-27
◦
F (15
◦
C)
Minimum Maintain Temperature of Soil:
50
◦
F (10
◦
C)
Maximum Foundation Temperature:
80
◦
F (27
◦
C)
Heater Cable Type:
Constant Wattage
81
PN 50316_0514