TLX48 HARDWARE ALARMS (Alarm Contacts)

TLX48 Power Supply Failure

Begin and Clear

Contact 1

A Power Supply has failed (Begin) or is restored (Clear).

Begin OID:

1,3,6,1,4,1,17658,3,14,0,27

Clear OID:

1,3,6,1,4,1,17658,3,14,0,28

Objects:

1: sysContact
2: sysDescr
3: sysLocation
4: sysName

TLX48 Fan Failure

Begin and Clear

Contact 2

A fan in the Fan Tray has failed (Begin) or is restored (Clear).

Begin OID:

1,3,6,1,4,1,17658,3,14,0,29

Clear OID:

1,3,6,1,4,1,17658,3,14,0,30

Objects:

1: sysContact
2: sysDescr
3: sysLocation
4: sysName

TLX48 High Temperature

Begin and Clear

Contact 3

The system has detected a temperature that is above the preset alarm threshold (Begin) or is now below the
preset alarm threshold (Clear).

Begin OID:

1,3,6,1,4,1,17658,3,14,0,31

Clear OID:

1,3,6,1,4,1,17658,3,14,0,32

Objects:

1: sysContact
2: sysDescr
3: sysLocation
4: sysName