Westermo GDW-11 User Manual

Page 10

Advertising
background image

10

6615-2203

GDW-11 EX / GDW-11 485 EX
Special condition for safe use

Ambient temperature:
This unit is designed for use in extreme ambient temperature conditions according to the following:
–25ºC ≤ Ta ≤ +50ºC

Installation in an apparatus cabinet:
This unit requires installation in an Ex certified apparatus cabinet suitable for the area of use and
providing a degree of protection of at least IP54.

Resistance to impact:
This unit requires installation in an apparatus cabinet where adequate resistance to impact is
provided by the apparatus cabinet. See "Installation in an apparatus cabinet" above for requirements
on the external apparatus cabinet.

Resistance to light:
This unit requires installation in an apparatus cabinet where it is protected from light (for example
daylight or light from luminaires). See "Installation in an apparatus cabinet" above for requirements
on the external apparatus cabinet.

Secureness of plugs:
When this unit is installed in an explosive atmospheres, all connectors must be mechanically secured
to prevent loosening.

Conductor temperature:
When this unit is installed in locations with high ambient temperature, special precautions shall be
taken upon the choice of external conductors and the temperature rating of the conductor(s).

Directive 94/9/EC alongside with other directives:
Directive 2004/108/EC (EMC) applies, to assure a safe performance of this unit under the scope
of Directive 94/9/EC, refer to the electromagnetic immunity level specified under "Type tests and
environmental conditions" in this manual.

Standards and date of compliance
EN 60079-0 and EN 60079-15
2011-06-30