Point to point over Ethernet
The continuous transfer of defined PROFIBUS I/O data over Ethernet, between one
FD-10 P (fieldbus adapter PROFIBUS DP Slave) and one FD-20 (Fieldbus adapter
PROFIBUS DP Master).

This application is created by using one FD-10 P (point to point mode) and one

ED-10 UDP (Ethernet adapter) in the main PROIBUS DP network and one ED-10 UDP
and one FD-20 in the remote network.The FD-20 can support a number of
PROFIBUS DP Slaves

FD-10 P

PR

OFIBUS DP

PR

OFIBUS DP

FD-20

PROFIBUS DP Master

ED-10 UDP

Ethernet

PROFIBUS DP Master

PROFIBUS DP Slave

ED-10 UDP

Configure ED-10:
Data rate the same as
FD-10 serial port.
Local IP : i.e:10.0.0.11
Remote IP: i.e: 10.0.0.12

Configure ED-10:
Data rate the same as
FD-20 serial.port
Local IP: i.e:10.0.0.12
Remote IP: i.e: 10.0.0.11

Master controlled transfer (Addressed)
The transfer of defined PROFIBUS I/O data between one FD-10 A controlled by a
PROFIBUS DP Master and several FD-20s.The FD-10 acts as serial transfer master
and can transfer I/O data between various addressed FD-20s.This solution is ideal
when a PROFIBUS DP Master needs to connect to two, or more, independent remote
PROFIBUS DP Slaves. A radio system, multi-drop modem or RS-485 bus is typically used
as the connecting medium.The serial data rate is independent of the PROFIBUS DP rate,
so each PROFIBUS DP network could run at different data rates to the serial backbone.

FD-10 A

PROFIBUS DP Slave

PROFIBUS DP Slave

PROFIBUS DP Master

Serial
master

Serial
slave

Serial
slave

PROFIBUS DP

PR

OFIBUS DP

PROFIBUS DP

FD-20

PROFIBUS DP Master

FD-20

PROFIBUS DP Master