9 Machine Integration

4/97

9.7.1 EMERGENCY STOP Connection Diagram

In case of a malfunction, the control-is-ready output should switch the 24 V supply voltage off.
Because this function is so critical, the TNC 122 checks this output each time the power supply is
switched on.

HEIDENHAIN recommends the following wiring:

+ -

TNC 122

Switch opens briefly when the control voltage

of each microprocessor is switched on

X41/10 X41/9

X41/28

"Control is

ready"

24V not
interruptible

"Control ready"
feedback

EMERGENCY
STOP
buttons

Control
voltage
on

k1

k1

K1

24 V

PLC

If the control is not to be part of the EMERGENCY STOP circuit, output X41/10 must be short-
circuited with input X41/28.