SMA WB 5000 Installation User Manual

Page 18

Advertising
background image

Installation requirements

SMA

Technology AG

Page 18

WB50_60-11:SE4005

Installation Guide

When choosing the installation site, be sure to note the
following:

When choosing the installation site, ensure there is enough space for heat to
dissipate. Under normal conditions, the following guidelines should be applied for
the space to be kept clear around the Windy Boy 5000 / 6000:

If you install the Windy Boy 5000 / 6000 in areas where high ambient temperatures
are to be expected, increase the distance between the devices. This will prevent the
individual Windy Boy 5000 / 6000 from drawing in the cooling air of the adjacent
device. Ensure that the inverter is sufficiently ventilated.

In domestic installations, the unit should not be mounted
on plasterboard walls, wooden boarding or similar as
otherwise audible vibrations are likely to result. The
Windy Boy 5000 / 6000 can make noises when in use
that may be irritating in a domestic setting.

Unintentionally pulling out the DC plug connector under load can
damage the plug and result in bodily injury or death! Install the
Windy Boy 5000 / 6000 in such a way that it is not possible (e.g.
for children) to unintentionally unplug the DC plug connector.

Individual components in the Windy Boy 5000 / 6000 can reach a
temperature of more than 60 °C. Ensure the unit is sufficiently far
away from combustible materials.

Do not install the Windy Boy 5000 / 6000 in potentially explosive
areas!

Minimum clearance

Sides

30 cm

Top

30 cm

Underneath

30 cm

In front

5 cm

30 cm

5

cm

30 cm

30
cm

30
cm

Windy

Boy

Netzwechselrichter für Windenergieanlagen

Netzwechselrichter für Windenergieanlagen

Grid tied inverter for wind turbines

Grid tied inverter for wind turbines

Pac 903W

Upv 330V

Advertising
This manual is related to the following products: