Cable losses of the windy boy 6000 – SMA WB 5000 Installation User Manual

Page 22

Advertising
background image

Installation requirements

SMA

Technology AG

Page 22

WB50_60-11:SE4005

Installation Guide

Cable losses of the Windy Boy 6000

The maximum cable lengths for the different cable cross-sections are as follows:

Conductor cross-section

4.0 mm²

6.0 mm²

10.0 m²

16 mm²

Max. length

10 m

15 m

25 m

41 m

0,0%

0,2%

0,4%

0,6%

0,8%

1,0%

1,2%

1,4%

0 m

10 m

15 m

20 m

25 m

30 m

35 m

40 m

45 m

50 m

5 m

4,0 mm²

6,0 mm²

10,0 mm²

16,0 mm²

Windy Boy 6000

Cable length

Loss

Do not use cable losses that exceed 1.0 %