Installation Guide
Cable losses of the Windy Boy 6000
The maximum cable lengths for the different cable cross-sections are as follows:
Conductor cross-section
4.0 mm²
6.0 mm²
10.0 m²
16 mm²
Max. length
10 m
15 m
25 m
41 m
0,0%
0,2%
0,4%
0,6%
0,8%
1,0%
1,2%
1,4%
0 m
10 m
15 m
20 m
25 m
30 m
35 m
40 m
45 m
50 m
5 m
4,0 mm²
6,0 mm²
10,0 mm²
16,0 mm²
Windy Boy 6000
Cable length
Loss
Do not use cable losses that exceed 1.0 %