Cable losses of the windy boy 5000 – SMA WB 5000 Installation User Manual

Page 21

Advertising
background image

SMA

Technology AG

Installation requirements

Installation Guide

WB50_60-11:SE4005

Page 21

The mains grid impedance at the AC input of the Sunny Boy 3800 must be less than
1 Ohm or the protective equipment may not work properly. In addition, we
recommend dimensioning the conductor cross-section so that line losses do not
exceed 1% at the nominal power. Line losses depending on the cable length and
cross-section are shown in the graph below. Multi-wire cables with copper forward
and return conductors are used.

Cable losses of the Windy Boy 5000

The maximum cable lengths for the different cable cross-sections are as follows:

Conductor cross-section

4.0 mm²

6.0 mm²

10.0 m²

16 mm²

Max. length

12 m

18 m

31 m

49 m

0,0%

0,2%

0,4%

0,6%

0,8%

1,0%

1,2%

1,4%

0 m

10 m

15 m

20 m

25 m

30 m

35 m

40 m

45 m

50 m

5 m

4,0 mm²

6,0 mm²

10,0 mm²

16,0 mm²

Windy Boy 5000

Do not use cable losses that exceed 1.0 %

Cable length

Loss