6 Related Parameters

6

Related Parameters

The parameters outlined in the following sections are used to set up the drive for operation

with the option. Set parameters as needed. Parameter setting methods can be found in the

drive Quick Start Guide or Technical Manual.

Parameter F2-01

Set parameter F2-01 to select between separate input channels or combined inputs on the

option.

Setting 0: Separate Input Channels (default)

This setting replaces drive analog inputs A1, A2, and A3 with higher resolution signals in

terminals V1, V2, and V3 on the option.
H3-†† parameters set the function, gain, and bias for V1, V2, and V3. Refer to the drive

Technical Manual for details on setting these parameters.

Note: 1. When F2-01 = 0, the option cannot be selected as frequency reference source. Setting b1-01 to 3

(Option PCB as Frequency Reference Selection) when F2-01 is set to 0 will trigger an oPE05 error.

2. When F2-01 is set to 0, the drive automatically detects the selected signal level for each input.

Parameters H3-01, H3-05, and H3-09 do not need to be set, and the previous settings for these

parameters are disregarded.

Figure 12

Figure 12 Using the Option for Multi-Function Analog Inputs

AI-A3

V1 voltage input

(–10 to 10 V)

or

current input

4 to 20 mA)

AI-A3

V2 voltage input

(–10 to 10 V)

or

current input

4 to 20 mA)

AI-A3

V3 voltage input

(–10 to 10 V)

or

current input

4 to 20mA)

Current input

(“I” position)

Voltage input

(“V” position)

Current input

(“I” position)

Voltage input

(“V” position)

Current input

(“I” position)

Voltage input

(“V” position)

T=H3-13

1

1+sT

Terminal V1 input switch

(S1)

Terminal V2 input switch

(S2)

Terminal V3 input switch

(S3)

H3-13

≠0

≠0

≠0

T=H3-13

1

1+sT

H3-13

H3-13

T=H3-13

1

1+sT

0

H3-08

H3-07

10 V

H3-12

H3-11

10 V

Input value (%)

Input voltage

Input voltage

Input voltage

Input value (%)

Input value (%)

H3-04

H3-03

10 V

0

0

0%

100%

100%

-100%

0%

100%

100%

-100%

0%

100%

100%

-100%

Input value is

added to the

function selected

in H3-02

Input value is

added to the

function selected

in H3-10

Input value is

added to the

function selected

in H3-06

AI