6 Related Parameters

24

YASKAWA ELECTRIC

TOBP C730600 38C 1000-Series Option AI-A3 Installation Manual

Parameter Table

Table 5 Related Parameters

No.

(Addr.

Hex)

Name

Description

Values

F2-01

(38F)

Analog Input Option Operation

Selection

0: Separate channels. Option input terminals V1, V2,

and V3 replace drive input terminals A1, A2, and

A3.

1: Combined. Input signals to terminals V1, V2, and

V3 are added together to create the frequency

reference.

When F2-01 = 0, Frequency Reference Selection 1

(b1-01) must be assigned to 1 (analog input

terminals).

Default: 0

Range: 0, 1

F2-02

(368)

Option Input Terminal Gain

Sets the gain for the analog reference as a percentage

of the maximum output frequency.

Default: 100.0%

Min: -999.9

Max: 999.9

F2-03

(369)

Option Input Terminal Bias

Sets the bias for the analog reference as a percentage

of the maximum output frequency.

Default: 0.0%

Min: -999.9

Max: 999.9

H3-02

(434)

Terminal A1 Function Selection

Sets the function of terminal A1.

Default: 0

Range: 0 to 31

H3-03

(411)

Terminal A1 Gain Setting

Sets the level of the input value selected in H3-02

when 10 V is input at terminal A1.

Default: 100.0%

Min: -999.9

Max: 999.9

H3-04

(412)

Terminal A1 Bias Setting

Sets the level of the input value selected in H3-02

when 0 V is input at terminal A1.

Default: 0.0%

Min: -999.9

Max: 999.9

H3-06

(414)

Terminal A3 Function Selection

Sets the function of terminal A3.

Default: 2

Range: 0 to 31

H3-07

(415)

Terminal A3 Gain Setting

Sets the level of the input value selected in H3-02

when 10 V is input at terminal A3.

Default: 100.0%

Min: -999.9

Max: 999.9

H3-08

(416)

Terminal A3 Bias Setting

Sets the level of the input value selected in H3-06

when 0 V s input at terminal A3.

Default: 0.0%

Min: -999.9

Max: 999.9

H3-10

(418)

Terminal A2 Function Selection

Sets the function of terminal A2.

Default: 0

Range: 0 to 31

H3-11

(419)

Terminal A2 Gain Setting

Sets the level of the input value selected in H3-10

when 10 V (20 mA) is input at terminal A2.

Default: 100.0%

Min: -999.9

Max: 999.9

H3-12

(41A) Terminal A2 Bias Setting

Sets the level of the input value selected in H3-10

when 0 V (0 or 4 mA) is input at terminal A2.

Default: 0.0%

Min: -999.9

Max: 999.9