6 Related Parameters

YASKAWA ELECTRIC

TOBP C730600 38C 1000-Series Option AI-A3 Installation Manual

23

Setting 1: Combined Inputs

This setting combines the three input signals of the option into one frequency reference

signal as illustrated in

Figure 13

.

Set parameter b1-01 to 3 and set parameters F2-02 and F2-03 to set the gain and bias settings

for the combined input signal. Pay special attention to the internal gains and interaction

among inputs as indicated in

Figure 13

when setting this function.

Figure 13

Figure 13 Combining Inputs for the Frequency Reference

Adjusting Input Levels with F2-02 and F2-03

The gain set to parameter F2-02 along with the combined input signal determines the

percentage of maximum output frequency used as the frequency reference when the bias set

to F2-03 is 0.

Note: For a single channel, a voltage input of 10 V or a current input of 20 mA is referred as 100%

The bias set to parameter F2-03 determines the percentage of the maximum output

frequency used as the frequency reference when the combined input signal is 0%.

Note: For a single channel, a voltage input of 0 V or a current input of 4 mA is referred as 0%

Example 1: If the gain in F2-02 is set to 50% and the bias in F2-03 is set to 0%, a combined

input signal of 100% yields a frequency reference 50% of the maximum frequency

reference. A combined input of 200% yields a frequency reference equal to the maximum

output frequency.
Example 2: If the gain in F2-02 is set to 200% and the bias in F2-03 is set to 0%, a combined

input signal of 50% yields a frequency reference equal to the maximum output frequency.

Increasing the input signal will not create a higher reference since maximum frequency

reference has already been reached.
Example 3: If the bias in F2-02 is set to 30% and the gain in F2-03 is set to 100%, a 0%

combined signal yields a frequency reference 30% of the maximum output frequency.

Inputting a combined reference of 70% will yield a reference of equal to the maximum

output frequency. Increasing the input signal will not create a higher reference since

maximum frequency reference has already been reached.

+

+

+

+

+