Related Drive Parameters

The following parameters are used to set up the drive for operation with the option. Parameter

setting instructions can be found in the drive Quick Start Guide or Technical Manual.
Confirm proper setting of the all parameters in

Table 6

before starting network

communications. After changing parameter settings, cycle power to the drive for the new

settings to take effect.

Table 6 Related Parameters

No.

Name

Description

Values

b1-01

<1>

Frequency Reference

Selection

Selects the frequency reference input source.

0: Operator - Digital preset speed d1-01 to d1-17

1: Terminals - Analog input terminal A1 or A2

2: MEMOBUS/Modbus communications

3: Option PCB

4: Pulse Input (Terminal RP)

Default: 1

Range: 0 to 4

(Set to 3 for BACnet)

b1-02 Run Command

Selection

Selects the run command input source.

0: Digital Operator - RUN and STOP keys

1: Digital input terminals S1 to S7

2: MEMOBUS/Modbus communications

3: Option PCB

Default: 1

Range: 0 to 3

(Set to 3 for BACnet)

F6-45 Drive Node Address

Sets the BACnet MS/TP MAC address (physical node

address).

Default: 1

Range: 0 to 127

F6-46 Communication

Speed Selection

Sets the communication speed.

0: 1200 bps

1: 2400 bps

2: 4800 bps

3: 9600 bps

4: 19200 bps

5: 38400 bps

6: 57600 bps

7: 76800 bps

8: 115200 bps

Default: 3

Range: 0 to 8

F6-47 Drive Transmit Wait

Time

Sets the time the drive waits after receiving data from a master

before transmitting response data.

Default: 5 ms

Range: 5 to 65

F6-48

<2>

BACnet Device

Object Identifier 0

Set the Instance Identifier of the BACnet Device Object, where

the F6-48 value is the least significant word.

Default: 1

Range: 0 to FFFFH

F6-49

<2>

BACnet Device

Object Identifier 1

Set the Instance Identifier of the BACnet Device Object, where

the F6-49 value is the most significant word.

Default: 0

Range: 0 to 3FH

<1>

To start and stop the drive with the option master device using serial communications, set b1-02 to 3. To control
the drive frequency reference via the master device, set b1-01 to 3.

<2>

These parameters set the Instance Identifier of the BACnet Device Object, where the F6-48 value is the least
significant word and the F6-49 value is the most significant word.
Example 1: Set the Device Object Instance Identifier of "1234". 1234 decimal is equal to 4D2H (hexadecimal).
Set F6-48 to 4D2H and F6-49 to 0.
Example 2: Set Device Object Instance Identifier to "1234567". 1234567 decimal is equal to 12D687H. Set
F6-48 to D687H and set F6-49 to 12H.

6 Related Drive Parameters

24

YASKAWA TOEP YEACOM 08A A1000 Option BACnet MS/TP SI-B3 Installation & Technical Manual