Troubleshooting

u

Drive-Side Error Codes

Drive-side error codes appear on the drive digital operator. Causes of the errors and corrective

actions are listed below. For additional error codes that may appear on the drive digital

operator, refer to the drive Technical Manual.

n

Faults

Both bUS (SI-B3 option communication error) and EF0 (External fault input from the SI-B3

option) can appear as an alarm or as a fault. When a fault occurs, the digital operator ALM

LED remains lit. When an alarm occurs, the ALM LED flashes.
If communication stops while the drive is running, use the following questions as a guide to

help remedy the fault:
• Is the option properly installed?
• Are the communication lines properly connected to the option? Are the wires loose?
• Is the controller program working? Has the controller/PLC CPU stopped?
• Did a momentary power loss interrupt communications?

Digital Operator Display

Fault Name

bUS

Option Communication Error
• The connection was lost after establishing initial communication.
• Only detected when the run command frequency reference is assigned to an

option card.

Cause

Possible Solution

No signal was received from the

PLC

• Check for faulty wiring.
• Correct the wiring.
• Check for disconnected cables and short circuits and repair as needed.

Faulty communications wiring or

an existing short circuit

Communication data error

occurred due to electrical

inteference

• Check the various options available to minimize the effects of noise.
• Counteract noise in the control circuit, main circuit, and ground wiring.
• Ensure that other equipment such as switches or relays do not cause electrical

inteference. Use surge absorbers if necessary.

• Use only recommended cables or other shielded line. Ground the shield on the

controller side or the drive input power side.

• Separate all communication wiring from drive power lines. Install an EMC

noise filter to the drive power supply input.

The option card is damaged

Replace the option card if there are no problems with the wiring and the error

continues to occur.